and the outdoor fan motor returns to its original state;
The above temperature points,
III.Anti
5.3.When the operation frequency F<40HZ, if the temperature of the outdoor
coiled pipe T outdoor coil≥52℃, the outdoor fan motor performs forced
During the
When T outdoor coil≤46℃, the compressor runs at the normal operating frequency, and the outdoor fan motor returns to its original state;
5.4.When the operation frequency F≥40HZ, if the temperature of the outdoor coiled pipe T outdoor coil≥57℃, the outdoor fan motor performs forced
During the
When T outdoor coil≤51℃, the compressor runs at the normal operating frequency, and the outdoor fan motor returns to its original state;
The above temperature points,
6.. Compressor discharge safeguard:
5 minutes after the compressor starts, when the compressor temperature rises above 105℃, decrease the compressor frequency by 2HZ/stop for 10 seconds, until the compressor temperature falls below 90℃, the compressor returns to normal operation;
When the compressor temperature rises above 115℃, the compressor should stop at once, wait until the compressor temperature falls below 90℃ and the waiting time period exceeds 3 minutes, the compressor returns to normal operation;
After the compressor restarts, if the compressor temperature rises above 115℃ once more within 15 minutes, the compressor should stop at once and give an alarm.
The temperature points are stored in EEPROM