Haier HSU-09HSA03/R2(DB) Frequency in the different mode, Control frequency in the same area

Models: HSU-12HSA03/R2(DB) HSU-09HSA03/R2(DB)

1 90
Download 90 pages 45.19 Kb
Page 12
Image 12
2.4.6 Frequency in the different mode

Haier air conditioner

Edition: 20070116

When the system is in test run, emergency operation, silencing operation mode, the DASH will be stopped.

2.4.5 Temperature adjustment section DASH operation condition in the different mode

2.4.6 Frequency in the different mode

In this area, the frequency (from indoor to outdoor) indication as following:

When the system is in the cool and dry mode, the frequencies between A area and B area are same. In the silencing operation mode, the frequencies between A-E area and F area are same.

 

Indication frequency

Scope of

Temperature

 

 

frequency

changing area

Heating

FQHOT [0—7]

30-140Hz

A—H

Heat in Silence mode

FQSHOT [0—2]

30-72Hz

F—H

 

 

 

 

Dry

FQDRY [0—7]

30-98Hz

B—H

Cooling

FQCOOL [0—7]

30-98Hz

B—H

Cooling in silence mode

FQSCOOL [0—2]

30-64Hz

F—H

The maximum frequency is the maximum frequency value as above table.

The max or min frequency in the cool or heat mode is corresponding with the max or min frequency value as the above table.

2.4.7 Control frequency in the same area

The compressor operating by the identity frequency for 3minutes that its area has no change, the indication frequency will be changed.

The timer will be reset when you input the different frequency. The system’s temperature area have no change when the system operating by new frequency for 3 minutes, please changing its indication frequency (add FQUPH or FQUPL).

- 12 -

Page 12
Image 12
Haier HSU-09HSA03/R2(DB), HSU-12HSA03/R2(DB) manual Frequency in the different mode, Control frequency in the same area