Haier HSU-12HSA03/R2(DB), HSU-09HSA03/R2(DB) 35.2, the fan motor will be weak speed operating

Models: HSU-12HSA03/R2(DB) HSU-09HSA03/R2(DB)

1 90
Download 90 pages 45.19 Kb
Page 15
Image 15
35.2, the fan motor will be weak speed operating);

Haier air conditioner

Edition: 20070116

Based on the heat exchange temperature to control the indoor fan as the above shown.

1.When the heat exchange temperature rise, to distinguish the fan speed based on the heat exchange temperature:

The heat exchange temperature is less than 35.2 , the speed of fan motor is weak (for the first power on, when the system operating in heat mode or OFF the defrost mode, and when the heat exchange temperature is less than 25.2 , the fan motor will OFF; if the temperature is between 25.2 and

35.2, the fan motor will be weak speed operating);

The fan motor operating with low speed when heat exchange temperature is between 35.2 and 37

The heat exchange temperature is more than 37 , fan motor operating by the set speed.

2.When drop of the heat exchange temperature, to distinguish the fan speed based on the heat exchange temperature:

The fan motor operating with low speed when heat exchange temperature is between 35.2 and

25.2;

The fan motor always operates with little-low speed when heat exchange temperature is less than

25.2. (for the first power on, when the system operating in heat mode or stopping the defrost mode,

and when the heat exchange temperature is between 25.2 and 16 , the fan motor will operating with weak speed; when the temperature is drop down to under16 , the fan motor will be stopped.

3. During the heat exchange temperature is rising fan speed is in the weak and low speed status, if the heat exchange temperature don’t return to previous value after 4 minutes, the fan speed will rise and continuously operating by the set temperature for 4 minutes, the system will adjustment the fan speed based on the heat exchange temperature;

4. When the heat exchange temperature is dropping down, the fan speed will go up to the set speed if the fan motor operate continuously by the low speed for more than 4 minutes.

- 15 -

Page 15
Image 15
Haier HSU-12HSA03/R2(DB), HSU-09HSA03/R2(DB) manual 35.2, the fan motor will be weak speed operating