Haier HSU-12HSA03/R2(DB), HSU-09HSA03/R2(DB) manual With this malfunction, LED1

Models: HSU-12HSA03/R2(DB) HSU-09HSA03/R2(DB)

1 90
Download 90 pages 45.19 Kb
Page 41
Image 41
With this malfunction, LED1

 

Haier air conditioner

Edition: 20070116

 

 

 

 

 

With this malfunction, LED1

1)The SPDU is broken

 

 

2)The power supply is not good

 

F22

on the outdoor mainboard

 

3) The system may have been over or under

 

 

blinks 3 times.

 

 

charged with gas

 

 

 

 

 

 

 

 

 

 

With the malfunction, LED1

1)IPM Module might be poorly radiated

 

 

on the outdoor mainboard

 

F1

2)IPM Module might be broken

 

blinks 2 times at frequency

 

 

3)Compressor might be broken

 

 

of 1 Hz

 

 

 

 

 

 

 

 

 

 

 

1)Check whether the indoor unit blows

 

 

With the malfunction, LED1

poorly due to blocked filters or poor

 

E9

on the outdoor mainboard

condition of the fan

 

blinks 21 times at frequency

2)The system is over charged with gas

 

 

 

 

of 1 Hz

3)Temperature of coil pipes on the indoor

 

 

 

unit too high

 

 

With outdoor EEPROM,

 

 

 

E4,F12

LED1 on the outdoor

1)E4 the indoor PCB might be damaged

 

mainboard blinks once at

2)F12 the outdoor PCB might be damaged

 

 

 

 

frequency of 1 Hz

 

 

 

 

 

 

 

 

 

1) Whether Terminal CN2 on the indoor

 

E14

/

mainboard is well inserted or not?

 

2) The indoor mainboard is damaged

 

 

 

 

 

 

3) The motor of the indoor unit is damaged

 

 

 

 

 

 

With the malfunction, LED1

1)The installation on terminal CN2 might be

 

 

not good

 

 

on the outdoor mainboard

 

F8

2)The

mainboard of the indoor unit is

 

blinks 9 times at frequency

 

 

damaged

 

 

of 1 Hz

 

 

3)The motor of the Outdoor unit is damaged

 

 

 

 

 

With the malfunction, LED1

1)The connection between IPM and the

 

 

outdoor PCB might be not good

 

 

on the outdoor mainboard

 

F3

2)The mainboard of the outdoor unit is

 

blinks 4 times at frequency

 

 

damaged

 

 

of 1 Hz

 

 

3)The IPM module is damaged

 

 

 

 

 

With the malfunction, LED1

1)The IPM module is damaged

 

 

2)Check power supply

 

 

on the outdoor mainboard

 

F19

3)The reactor of outdoor is damage

 

blinks 6 times at frequency

 

 

4)The rectifying bridge or IPM module is

 

 

of 1 Hz

 

 

damage

 

 

 

 

- 41 -

Page 41
Image 41
Haier HSU-12HSA03/R2(DB), HSU-09HSA03/R2(DB) manual With this malfunction, LED1