![](/images/new-backgrounds/1053655/5365543x1.webp)
6 Vent Clearances and Framing
A. Pipe Clearances to Combustibles | B. Wall Penetration Framing |
WARNING
Fire Risk. Explosion Risk.
Maintain vent clearance to combustibles as specified.
•Do not pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause fire.
NOTE: Slope | 3 in. TOP |
not required. | CLEARANCE |
| |
1 in. CLEARANCE |
|
AROUND VERTICAL | |
SECTIONS |
|
| 1 in. SIDE AND |
| BOTTOM CLEARANCE |
Figure 6.1 Pipe Clearances |
Note: Heat shields MUST overlap by a minimum of
The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102
mmto 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field trimmed. If wall thickness is greater than
HEAT
SHIELD3 in. TOP
CLEARANCE
HEAT SHIELD
7 in.
|
| 1 in. CLEARANCE | |
WALL | |||
BOTTOM & SIDES | |||
SHIELD | |||
| |||
FIRESTOP |
|
C
D
A*
B*
|
| A | B | C | D | |
in. | 36 1/2 | 24 3/8 | 35 1/2 | 23 3/8 | ||
mm | 927 | 619 | 902 | 594 | ||
|
*Shows center of vent framing hole for top or rear venting. The center of the hole is one (1) inch (25.4 mm) above the center of the horizontal vent pipe.
Figure 6.3 Exterior Wall Hole
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall shield firestop, (Figure 6.2) whenever a wall is penetrated. Use same size framing materials as those used in the wall construction. The wall shield firestop maintains minimum clearances and prevents cold air infiltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus- tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
WALL
Figure 6.2 Horizontal Venting Clearances to Combustible Materials
22 | Hearth & Home Technologies • |