D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing or finishing material closer than the minimums listed must be constructed entirely of noncom- bustible materials (i.e., steel studs, concrete board, etc).

All measurements are in inches.

8

7

6

5

4

3

4 5

12

11

10

9

6 7 8 9 10 11

CEILING

32

12 13

 

 

 

 

 

 

 

 

 

 

 

1/2 IN.

TOP VIEW

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-7/8 IN.

 

 

 

 

 

 

 

 

MINIMUM

 

 

3 FT. MAXIMUM

 

 

 

Note: Clearance from fireplace opening to perpendicular wall.

Figure 5.5 Mantel Leg (Acceptable on both sides of opening.)

TOP OF HOOD OR FIREPLACE OPENING

Figure 5.3 Minimum Vertical and Maximum Horizontal Dimensions of Combustibles

 

1/2 in.

3-1/2 in.

SHEETROCK

NON-COMBUSTIBLE

BOARD SHIPPED

WITH APPLIANCE

1/2 in.

NON-COMBUSTIBLE ZONE

Figure 5.4 Non-Combustible Zone

 

 

 

 

 

 

 

 

 

3 IN.

TOP VIEW

 

 

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-3/8 IN.

MINIMUM UNLIMITED

Note: Clearance from fireplace opening to perpendicular wall.

Figure 5.6 Wall Projection (Acceptable on one side of opening.)