B. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materi- als (i.e., steel studs, concrete board, etc.) Failure to comply could cause fire.

 

 

 

 

 

 

 

3 IN.

TOP VIEW

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All measurements are in inches.

8

7

6

5

4

3

4 5

12

11

10

9

6 7 8 9 10 11

CEILING

32

12 13

5-3/8 IN.

MINIMUM UNLIMITED

Note: Clearance from fireplace opening to perpendicular wall.

Figure 13.14 Wall Projection (Acceptable on one side of opening)

 

1/2 in.

3-1/2 in.

SHEETROCK

NON-COMBUSTIBLE

BOARD SHIPPED

TOP OF HOOD OR FIREPLACE OPENING

Figure 13.12 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

 

 

 

 

 

 

 

 

 

 

 

1/2 IN.

TOP VIEW

 

 

 

 

 

 

 

 

 

 

 

 

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-7/8 IN.

 

 

 

 

 

 

 

 

MINIMUM

 

 

3 FT. MAXIMUM

 

 

 

Note: Clearance from fireplace opening to perpendicular wall.

Figure 13.13 Mantel Leg (Acceptable on both sides of opening)

WITH APPLIANCE

1/2 in.

NON-COMBUSTIBLE ZONE

Figure 13.15 Non-Combustible Zone

Heat & Glo • SL-750TRSFHHIPI2156-900 Rev. F • 11/08

55

Page 55
Image 55
Hearth and Home Technologies SL-750TRSFHHIPI owner manual Wall Projection Acceptable on one side of opening