Top Vent - Vertical Termination - (continued)
Three 90º Elbows
Note: Use SLP Series components only.
Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 5.3).
| V1 | H1+ H2 Maximum |
| V2 | V1 + V2 Minimum | |||
90º Elbow | 0 | 0 |
| 457 mm | 457 mm | |||
1/2 ft.. | 152 mm | 1 ft. | 305 mm | * |
| * | * | * |
457 mm | 2 ft. | 610 mm | * |
| * | * | * | |
762 mm | 4 ft. | 1.2 m | * |
| * | * | * | |
1.1 m | 6 ft. | 1.8 m | * |
| * | * | * | |
|
|
|
|
|
|
|
|
|
1.4 m | 14 ft. | 4.3 m | * |
| * | * | * | |
|
|
|
|
|
|
|
|
|
H1 Maximum = 14 ft. (4.3 m)
*No specific restrictions on this value EXCEPT V1 + V2 + H1 + H2
CANNOT exceed 40 ft. (12.2 m).
V2
H1
H2 | V1 |
| |
| INSTALLED |
| HORIZONTALLY |
Figure 7.10