Top Vent - Horizontal Termination - (continued)
Two Elbows
Note: Use SLP Series components only.
Note: There MUST be a 25% reduction in total H when using flex vent except when using the simple up and out installation (see Figure 5.3).
V Minimum |
|
| H Maximum | ||
|
|
|
| ||
|
|
| |||
|
|
|
| ||
90º Elbow |
|
| NOT ALLOWED | ||
1/2 ft.* |
| 152 mm | 1 ft. |
| 305 mm |
| 457 mm | 2 ft. |
| 610 mm | |
| 762 mm | 4 ft. |
| 1.2 m | |
| 1.1 m | 6 ft |
| 1.8 m | |
| 1.4 m | 14 ft. |
| 4.3 m |
H1 + H2 Maximum= 14 ft. (4.3 m)
V1 + H1 + H2 Maximum= 40 ft. (12.2 m)
* See warning below
WARNING *
Fire Risk.
• When using
SStermination caps on top vented fireplaces, a one foot minimum vertical vent section is
required before installing first elbow.
•When using
H2 | V1 | |
H1 | ||
|
INSTALLED
HORIZONTALLY
Figure 7.5