WARNING:FOLLOW NATIONAL REGULATIONS

 

AND CODES OF PRACTICE FOR MINIMUM CLEAR-

 

ANCES FROM GAS TERMINALS, AND PLACE-

 

MENT OF GAS TERMINAL.

NOTE

This also pertains to vertical flue systems installed on

 

the outside of the building.

TERMINATION

CAP

51 cm

VERTICAL

WALL

LOWEST

DISCHARGE

OPENING

X

30,5 cm

ROOF PITCH

IS X/ 30,5 cm

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

Angle

H (Min.) M

0°-26.6°

............................................... 0.30*

26.6°-30.3°

............................................... 0.38*

30.3°-33.7°

............................................... 0.46*

33.7°-36.9°

............................................... 0.61*

36.9°-39.8°

............................................... 0.76

39.8°-42.5°

............................................... 0.99

42.5°-45.0°

............................................... 1.22

45.0°-49.4°

............................................... 1.52

49.4°-53.1°

............................................... 1.83

53.1°-56.3°

............................................... 2.13

56.3°-59.0°

............................................... 2.29

59.0°-60.3°

............................................... 2.44

*.91 M minimum in snow regions

Figure 24. Minimum Height from Roof to Lowest Discharge Opening

Heat & Glo • 6000TRS-CE2049-900 Rev. Q • 2/11

27

Page 27
Image 27
Heat & Glo LifeStyle 6000TRS-CE manual Outside of the building