Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

CXM Process Flow Chart

WARNING!

WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.

Failure to disconnect power before servicing can cause severe personal injury or death.

 

 

 

Start

 

 

 

 

 

 

 

Did Unit

 

 

 

Attempt to

 

 

 

Start?

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

Did Unit

 

 

 

Lockout at

 

 

 

Start-up?

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

See “Unit

 

Yes

Unit Short

short

 

 

 

Cycles?

cycles”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

CXM Functional Troubleshooting Flow Chart

No

 

 

Check Main

 

 

 

 

 

 

 

 

 

 

 

power (see power

 

 

 

 

 

 

 

 

 

 

 

 

 

problems)

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check fault LED code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on control board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See HP

 

 

See

 

 

See FP1

 

 

 

 

 

 

 

LP/LOC

 

 

Fault

 

 

 

 

 

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No fault

shown

Replace

CXM

See “Only Yes Fan Runs”

See “Only Yes

Comp

Runs”

See “Does No not Operate

in Clg”

Only Fan

Runs?

No

Only

Compressor

Runs?

No

Did unit lockout after a period of operation?

No

Does unit operate in cooling?

Yes

See FP2

 

See

 

See Over/

Fault

 

Condensate

 

Under

 

 

Fault

 

Voltage

Yes

Unit is OK!

‘See Performance

Troubleshooting’ for

further help

44

Page 44
Image 44
Heat Controller HTD, HTV, HTH manual CXM Functional Troubleshooting Flow Chart, CXM Process Flow Chart