Installation, Operation & Maintenance | HTV/HTD/HTH SERIES | Heat Controller, Inc. |
Electrical - Low Voltage Wiring
Thermostat Connections
The thermostat should be wired directly to the CXM board (units with PSC fan). Units with optional ECM motor include factory wiring from the CXM board to the ECM interface board. Thermostat wiring for these units should be connected to the ECM interface board. Figure 18 shows wiring for TT/ HTTS units with PSC or optional ECM motor. See “Electrical – Thermostat” for speciÄc terminal connections.
Figure 18: HTT/TSLowLowVoltageVoltageFieldFieldWiringWiring
Low voltage Äeld wiring for units with
PSC FAN (ECM board will not be present)
Low voltage Äeld wiring for units with ECM fan
Low Water Temperature Cutout Selection
The CXM control allows the Äeld selection of low water (or
The factory setting for FP1 is for systems using water (30°F
an antifreeze solution. All residential units include water/ refrigerant circuit insulation to prevent internal condensation, which is required when operating with entering water temperatures below 59°F [15°C].
Figure 19: FP1 Limit Setting
| |
| jumper should |
| be clipped for |
CXM PCB | low temperature |
operation |