Performance Troubleshooting

Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

Performance Troubleshooting

Performance Troubleshooting

Htg

Clg

Possible Cause

Solution

 

X

X

Dirty filter

Replace or clean.

 

 

 

 

Check for dirty air filter and clean or replace.

 

X

 

 

 

 

 

Reduced or no air flow in heating

Check fan motor operation and airflow restrictions.

 

 

 

 

Too high of external static. Check static vs. blower table.

 

 

 

 

 

 

 

 

 

Check for dirty air filter and clean or replace.

 

 

X

 

 

 

 

Reduced or no air flow in cooling

Check fan motor operation and airflow restrictions.

 

 

 

 

Too high of external static. Check static vs. blower table.

Insufficient capacity/ Not

 

 

 

 

X

X

Leaky duct work

Check supply and return air temperatures at the unit and at distant duct registers

cooling or heating

if significantly different, duct leaks are present.

 

 

 

 

X

X

Low refrigerant charge

Check superheat and subcooling per chart.

 

X

X

Restricted metering device

Check superheat and subcooling per chart. Replace.

 

 

X

Defective reversing valve

Perform RV touch test.

 

X

X

Thermostat improperly located

Check location and for air drafts behind stat.

 

X

X

Unit undersized

Recheck loads & sizing. Check sensible clg. load and heat pump capacity.

 

X

X

Scaling in water heat exchanger

Perform scaling check and clean if necessary.

 

X

X

Inlet water too hot or too cold

Check load, loop sizing, loop backfill, ground moisture.

 

 

 

 

Check for dirty air filter and clean or replace.

 

X

 

Reduced or no air flow in heating

 

 

 

Check fan motor operation and air flow restrictions.

 

 

 

 

Too high of external static. Check static vs. blower table.

 

 

 

 

 

 

 

X

Reduced or no water flow in cooling

Check pump operation or valve operation/setting.

 

 

 

 

 

Check water flow. Adjust to proper flow rate.

 

 

 

 

High Head Pressure

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

X

 

Air temperature out of range in heating

Bring return air temperature within design parameters.

 

 

X

Scaling in water heat exchanger

Perform scaling check and clean if necessary.

 

X

X

Unit overcharged

Check superheat and subcooling. Re-weigh in charge.

 

X

X

Non-condensables in system

Vacuum system and re-weigh in charge.

 

X

X

Restricted metering device.

Check superheat and subcooling per chart. Replace.

 

 

 

 

Check pump operation or water valve operation/setting.

 

X

 

Reduced water flow in heating.

 

 

 

Plugged strainer or filter. Clean or replace.

 

 

 

 

Check water flow. Adjust to proper flow rate.

 

 

 

 

 

 

X

 

Water temperature out of range.

Bring water temperature within design parameters.

Low Suction Pressure

 

 

 

Check for dirty air filter and clean or replace.

 

 

X

Reduced air flow in cooling.

Check fan motor operation and air flow restrictions.

 

 

 

 

Too high of external static. Check static vs. blower table.

 

 

 

 

 

 

 

X

Air temperature out of range

Too much cold vent air? Bring entering air temperature within design parameters.

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low Discharge Air Temperature

X

 

Too high of air flow

Check fan motor speed selection and air flow chart.

in Heating

X

 

Poor performance

See ‘Insufficient Capacity’

High humidity

 

X

Too high of air flow

Check fan motor speed selection and airflow chart.

 

X

Unit oversized

Recheck loads & sizing. Check sensible clg load and heat pump capacity.

 

 

46