Unit Commissioning And Operating Conditions

Operating Limits

Environment – Units are designed for indoor installation only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).

Power Supply – A voltage variation of +/– 10% of nameplate utilization voltage is acceptable.

Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. 2) water temperature, and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to insure proper unit operation. Extreme variations in temperature and humidity and/or corrosive water or air will adversely affect unit performance, reliability, and service life. Consult Table 8a for operating limits.

Table 8a: Building Operating Limits

 

Limits

 

 

TTUnitHT

 

 

 

pOperatingLimits

 

Cooling

 

Heating

 

 

 

Cooling

 

 

Air mLimits

 

 

 

 

 

 

 

Min. ambient air, DB

 

45ºF [7ºC]

 

39ºF [4ºC]

 

mbient air, DB

 

45ºF [7ºC]

39ºF [4ºC]

 

Rated ambient air, DB

 

80.6ºF [27ºC]

68ºF [20ºC]

 

ambient air, DB

 

80.6ºF [27ºC]

68ºF [20ºC]

 

Max. ambient air, DB

 

130ºF [54ºC]

85ºF [29ºC]

 

mbient air, DB

 

130ºF [54ºC]

85ºF [29ºC]

 

Min. entering air, DB/WB

 

65/45ºF [18/7ºC]

50ºF [10ºC]

 

tering air, DB/WB

 

60/45ºF [16/7ºC]

40ºF [4.4ºC]

 

entering air, DB/WB

 

70/50ºF Reheat

68ºF [20ºC]

 

 

80.6/66.2ºF [27/19ºC]

 

Rated entering air, DB/WB

 

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

 

ntering air, DB/WB

 

100/75ºF [38/24ºC]

80ºF [27ºC]

 

Max. entering air, DB/WB

 

100/75ºF [38/24ºC]

80ºF [27ºC]

 

Limits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Limits

 

30ºF [-1ºC]

20ºF [-6.7ºC]

 

tering water

 

 

Min. entering water

 

20ºF [-6.7ºC]

20ºF [-6.7ºC]

 

entering water

 

50-110ºF [10-43ºC]

30-70ºF [-1 to

 

Normal entering water

 

50-110ºF [10-43ºC]

30-70ºF [-1 to 21ºC]

 

Maxntering. enteringwaterwater

 

120ºF120ºF[49ºC][49ºC]

120ºF90ºF [32ºC][49ºC]

 

NormalWaterWaterFlowFlow

 

1.15.5toto3.30.0gpm/ /ton

 

 

 

[1[1.6.6toto3.32.2l/ml/mperkW]

 

 

 

 

 

 

 

 

 

 

 

Commissioning Conditions

Consult Table 8b for the particular model. Starting conditions vary depending upon model and are based upon the following notes:

Notes:

1.Conditions in Table 8b are not normal or continuous operating conditions. Minimum/maximum limits are start-up conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under these conditions on a regular basis.

2.Voltage utilization range complies with AHRI Standard 110.

Table 8b: Building Commissioning Limits

Commissioning Limits

UnitHT

Cooling

Heating

 

 

Air Limits

 

 

Min. ambient air, DB

45ºF [7ºC]

39ºF [4ºC]

Rated ambient air, DB

80.6ºF [27ºC]

68ºF [20ºC]

Max. ambient air, DB

130ºF [54ºC]

85ºF [29ºC]

Min. entering air, DB/WB

60ºF [16ºC]

40ºF [4.5ºC]

Rated entering air, DB/WB

80.6/66.2ºF [27/19ºC]

68ºF [20ºC]

Max. entering air, DB/WB

110/83ºF [43/28ºC]

80ºF [27ºC]

Water Limits

 

 

 

Min. entering water

20ºF [-6.7ºC]

20ºF [-6.7ºC]

Normal entering water

50-110ºF [10-43ºC]

30-70ºF [-1 to 21ºC]

Max. entering water

 

120ºF [49ºC]

120ºF [49ºC]

Normal Water Flow

1.5 to 3.0 gpm / ton

[1.6 to 3.2 l/m per kW]

 

 