Installation, Operation & Maintenance

HTV/HTD/HTH SERIES

Heat Controller, Inc.

CXM Controls

Table 7: Nominal resistance at various temperatures

Temp (ºC)

Temp (ºF)

Resistance

Temp (ºC)

Temp (ºF)

Resistance

(kOhm)

(kOhm)

 

 

 

 

-17.8

0.0

85.34

55

131.0

2.99

-17.5

0.5

84.00

56

132.8

2.88

-16.9

1.5

81.38

57

134.6

2.77

-12

10.4

61.70

58

136.4

2.67

-11

12.2

58.40

59

138.2

2.58

-10

14.0

55.30

60

140.0

2.49

-9

15.8

52.38

61

141.8

2.40

-8

17.6

49.64

62

143.6

2.32

-7

19.4

47.05

63

145.4

2.23

-6

21.2

44.61

64

147.2

2.16

-5

23.0

42.32

65

149.0

2.08

-4

24.8

40.15

66

150.8

2.01

-3

26.6

38.11

67

152.6

1.94

-2

28.4

36.18

68

154.4

1.88

-1

30.2

34.37

69

156.2

1.81

0

32.0

32.65

70

158.0

1.75

1

33.8

31.03

71

159.8

1.69

2

35.6

29.50

72

161.6

1.64

3

37.4

28.05

73

163.4

1.58

4

39.2

26.69

74

165.2

1.53

5

41.0

25.39

75

167.0

1.48

6

42.8

24.17

76

168.8

1.43

7

44.6

23.02

77

170.6

1.39

8

46.4

21.92

78

172.4

1.34

9

48.2

20.88

79

174.2

1.30

10

50.0

19.90

80

176.0

1.26

11

51.8

18.97

81

177.8

1.22

12

53.6

18.09

82

179.6

1.18

13

55.4

17.26

83

181.4

1.14

14

57.2

16.46

84

183.2

1.10

15

59.0

15.71

85

185.0

1.07

16

60.8

15.00

86

186.8

1.04

17

62.6

14.32

87

188.6

1.01

18

64.4

13.68

88

190.4

0.97

19

66.2

13.07

89

192.2

0.94

20

68.0

12.49

90

194.0

0.92

21

69.8

11.94

91

195.8

0.89

22

71.6

11.42

92

197.6

0.86

23

73.4

10.92

93

199.4

0.84

24

75.2

10.45

94

201.2

0.81

25

77.0

10.00

95

203.0

0.79

26

78.8

9.57

96

204.8

0.76

27

80.6

9.16

97

206.6

0.74

28

82.4

8.78

98

208.4

0.72

29

84.2

8.41

99

210.2

0.70

30

86.0

8.06

100

212.0

0.68

31

87.8

7.72

101

213.8

0.66

32

89.6

7.40

102

215.6

0.64

33

91.4

7.10

103

217.4

0.62

34

93.2

6.81

104

219.2

0.60

35

95.0

6.53

105

221.0

0.59

36

96.8

6.27

106

222.8

0.57

37

98.6

6.01

107

224.6

0.55

38

100.4

5.77

108

226.4

0.54

39

102.2

5.54

109

228.2

0.52

40

104.0

5.33

110

230.0

0.51

41

105.8

5.12

111

231.8

0.50

42

107.6

4.92

112

233.6

0.48

43

109.4

4.72

113

235.4

0.47

44

111.2

4.54

114

237.2

0.46

45

113.0

4.37

115

239.0

0.44

46

114.8

4.20

116

240.8

0.43

47

116.6

4.04

117

242.6

0.42

48

118.4

3.89

118

244.4

0.41

49

120.2

3.74

119

246.2

0.40

50

122.0

3.60

120

248.0

0.39

51

123.8

3.47

121

249.8

0.38

52

125.6

3.34

122

251.6

0.37

53

127.4

3.22

123

253.4

0.36

54

129.2

3.10

 

 

 

CXM Thermostat Details

Thermostat Compatibility - Most all heat pump thermostats can be used with the CXM control. However Heat/Cool stats are

NOT compatible with the CXM.

Anticipation Leakage Current - Maximum leakage current for "Y" is 50 mA and for "W" is 20mA. Triacs can be used if leakage current is less than above. Thermostats with anticipators can be used if anticipation current is less than that specified above.

Thermostat Signals -

"Y" and "W" have a 1 second recognition time when being activated or being removed.

"O" and "G" are direct pass through signals but are monitored by the micro processor.

"R" and "C" are from the transformer.

"AL1" and "AL2" originate from the alarm relay.

"A" is paralleled with the compressor output for use with well water solenoid valves.

The "Y" 1/4" quick connect is a connection point to the "Y" input terminal P1 for factory use. This "Y" terminal can be used to drive panel mounted relays such as the loop pump relay.

30

Page 30
Image 30
Heat Controller HTV, HTH Nominal resistance at various temperatures, CXM Thermostat Details, Not compatible with the CXM