Programming & Reviewing
Programming And Reviewing Settings / Changes (cont’d.)
Use the “PROGRAM REVIEW” button to select these items:
•Defrost Type –
•Refrigerant Type - “rEF” - Selection for type of refrigerant -
•Box Temperature - “bot” - Select box temperature setpoint. Selection range is
•Superheat - “SUP” - Evaporator superheat is controlled by the board on each evaporator. Each board measure the evaporator saturation suction temperature and the suction pressure to determine the superheat. The superheat value at the evaporator can be changed to ensure a 20°F to 30°F superheat at the Compressor. Default: 8°F.
•Evaporator Board: Slave? - “SLA” - On multiple evaporator systems, each evaporator board has to be programmed to be a Master or a Slave.
Each board is shipped from our factory set as a Master. You must make this change to each Slave evaporator. A selection of “YES” is made for this setting.
The default for each board is a Master, so on Single Evaporator systems no change is required.
•No. of Defrost per Day - “dFn” - A selection must be made for the number of defrosts cycles per day – 1,2,3,4,5,6,8,10 or 12 per day. If no
selection is made, Defaults: electric defrost 4 per day and air defrost 2 per day.
•Defrost
has expired. On multiple evaporator systems this is controlled by the Master unit. Each board should have the same setting. Defaults: electric defrost 30 minutes and air defrost 40 minutes.
•Defrost End Temperature - “dFt” - This is the temperature at which the Defrost will be terminated. Defaults: electric defrost +60°F and air Defrost +45°F.
•Defrost Delay Start Time - “dFS” - This allows the delay of the start of the first defrost. Defaults: 0.5 hours to 23.5 hours.
•Alarm High Temperature - “ALH” - Temperature at which a high box temperature alarm will be triggered. This does not apply during defrost. Defaults: electric defrost +5°F and air defrost +50°F.
•Alarm Low Temperature - “ALL” - Temperature at which a Low Box Temperature alarm will be triggered. Defaults: Electric Defrost
•Alarm Time - “ALt” - Time which High Temperature or Low Temperature condition must exceed before alarm is triggered. Default:
60 minutes.
•°F/°C -
•When °C is selected a red dot will appear in the right bottom corner of the LED display of the Beacon II board.