Configuration

Configuration

Multiple Evaporator Configuration (Master/slave)

If there are multiple evaporators on a system, the

program for each SLAVE evaporator must be changed to identify it as a SLAVE. To do so, press the “PROGRAM REVIEW” button repeatedly until “SLA” appears then use the “SELECT” knob to select “YES” then press “ENTER”. All Beacon II boards are shipped with the

PROGRAM

REVIEW

factory default as a MASTER evaporator. Place all boards in the “SERVICE” mode while you program the setpoints to avoid errors and alarms which may cause

troubles at startup.

VERY IMPORTANT: This must be done for each slave board.

SELECT

Up to 4 evaporators can be connected as a master/slave configuration. DO NOT remove the room sensor from any of the Beacon II boards.

This also applies when connected to the optional Smart Controller.

CU

M

S

S

S

M = Master Evaporator S = Slave Evaporator

CU = Condensing Unit

Each Beacon II board power is supplied by a transformer in the evaporator on which

it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.