Heatcraft Refrigeration Products H-IM-79E Defrost / Alarms, Electric Defrost Mode, Alarm Codes

Models: H-IM-79E

1 36
Download 36 pages 38.25 Kb
Page 18
Image 18
Defrost / Alarms

Defrost / Alarms

Electric Defrost Mode

When a defrost is initiated, the EEV closes, the compressor is allowed to pumpdown and shut off. The evaporator fans are cycled off and the defrost heaters are energized.

On multiple evaporator systems, all controllers must terminate their defrost, either on temperature or fail-safe time, before the master controller will end the defrost cycle.

There is a 2 minute condensate drain-down period after which the compressor is started for a refreeze period. The evaporator fan stays off (fan delay). The refreeze period will last until the evaporator suction temperature is at 28°F or 3 minutes has elapsed. After this sequence, the system is back in the refrigerating mode and evaporators fans are now running.

Air Defrost Mode

The sequence is the same as for electric defrost except that there are no heaters and the evaporator fans run continuously. If the air defrost for motors are wired through the fan relay on the board, they will remain energized during defrost mode.

Alarms

Beacon provides a set of dry contacts for use in signaling an alarm. These contacts can be connected to a light, a buzzer, a bell etc., which will be activated when an alarm condition occurs. When the Beacon II is energized, the alarm contacts are OPENED. When an alarm condition is detected, the contacts are CLOSED.

Conditions under which the alarm contacts will close are:

High Box Temperature – LED Display: A 1 - Room temperature has exceeded the Alarm High ALH value for the Alarm time ALt, programmed.

Low Box Temperature - LED Display: A 2 - Room temperature has dropped below the Alarm Low ALL value for the Alarm time ALt, programmed

System Start-up failure – LED Display: A 3 - Compressor pumps down and tries to restart after 4 minutes. After 4

unsuccessful attempts to restart, the alarm code A 3 is displayed. System continues trying to restart.

Input Fault – LED Display: A 4 - Box Temp., Suction Temp., Pressure Transducer open or not installed.

Power failure – Loss of power to the Evaporator

Alarm Codes

A 1 High Box Temp

A 2 Low Box temp

A 3 System Start-up failure

Compressor pumps down and tries to restart after 4 minutes

A 4 Input Fault

Box Temp., Suction Temp., Pressure

Transducer open or not installed

Clearing Alarms

Alarms A1 – High Box Temp. and A2 – Low Box Temp. will clear automatically if the Box Temp. decreases

or increases to below or above the Alarm setpoint temperature. Placing the system in the “SERVICE MODE” or turning off power will clear the A3 Alarm. Replacing the Room Sensor, Suction Sensor or Pressure

Transducer will clear the A4 Alarm.

18

Page 18
Image 18
Heatcraft Refrigeration Products H-IM-79E manual Defrost / Alarms, Electric Defrost Mode, Air Defrost Mode, Alarm Codes