Heatcraft Refrigeration Products H-IM-79E manual Expansion Valve Capacity, Diagnostics

Models: H-IM-79E

1 36
Download 36 pages 38.25 Kb
Page 24
Image 24
Expansion Valve Capacity

Expansion Valve Capacity

 

 

 

 

R-22

 

 

R-404A / R-507

 

 

 

 

Evaporator Temperature (°F.)

Evaporator Temperature (°F.)

 

 

 

+20

 

-20

+20

 

 

-20

Part Number

Valve

Pressure Drop Across Valve (psi)

Pressure Drop Across Valve (psi)

100

BTUH

100

BTUH

100

BTUH

100

BTUH

29320003

ESVB-1

0.68

8160

0.64

7680

0.48

5760

0.42

5040

29320004

ESVB-4

3.27

39240

3.07

36840

2.31

27720

2.05

24600

29320007 - 08

ESVB-10

8.02

96240

7.54

90480

5.65

67800

5.01

60120

29320013

ESVB-15

15.14

181680

14.25

171000

10.69

128280

9.47

113640

29320014

ESVB-20

22.18

266160

20.87

250440

15.65

187800

13.86

166320

Diagnostics

Beacon II Troubleshooting Guide

PROBLEM

Step

ACTION ITEM

IF OK

IF NOT OK

 

 

1.

Check Primary Power Supply Disconnect

 

1.

Check fuses and circuit breakers

 

 

2.

Check Voltage to Evaporator Transformer

Go to

2.

Check field wiring for breaks

LED is not lit.

3.

Check Transformer Secondary Output Volts

next step

3.

Replace if necessary

 

 

4.

Check Voltage at Control Board (24V and C)

 

4.

Check factory wiring and connections

 

 

5.

Replace Control Board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check Compressor internal overloads

 

1.

Wait for reset

LED shows Coo, but

2.

Check Control Power to Condensing Unit

 

2.

Check transformer voltage (secondary and

 

 

 

(24 Volts across “COMP” and “C” at board)

Go to

 

primary) and wiring of 208V power taps.

compressor will not run.

3.

Check Compressor Contactor Coil Voltage

next step

3.

Check internal condensing unit wiring

 

 

4.

Check Compressor Contactor “pulled in”

 

4.

Replace as needed

 

 

 

 

 

 

 

 

 

ERROR CODES:

 

 

 

 

 

 

 

E1 Room Sensor

 

 

 

Check Sensor and Board Connection

 

Replace as needed

E2 Defrost Sensor

 

 

 

Check Sensor and Board Connection

 

Replace as needed

E3 Suction Sensor

 

 

 

Check Sensor and Board Connection

 

Replace as needed

E4 Suction Transducer

 

 

 

Check Transducer and Board Connection

 

Replace as needed

E5 Outdoor Sensor

 

 

 

Check Sensor, wiring and Board Connection

 

Replace or remove

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check Refrigerant Type

 

1.

Compare board setpoint and refrigerant

 

 

 

2.

Check coil for ice

 

2.

Defrost coil and check defrost cycle

 

 

 

 

 

 

 

 

settings/setpoints, defrost sensor and

E6 Low Superheat

 

 

 

 

 

 

 

heater amps.

 

 

3.

Check Control Board step position from board LED

 

3. Replace board if EEV steps not at 2.

 

 

 

During Cooling

 

4.

Check Electric Expansion Valve Closure

Go to

4.

Pumpdown system see if LPS opens or if it

(0°F for 2 minutes)

 

 

 

 

next step

 

times out (EEV is bad or LPS is set

 

 

 

 

 

 

 

 

incorrectly, if times out) – See Pumpdown.

 

 

 

5.

Compressor Not Operating

 

5.

Check overloads and contactor.

 

 

 

6.

Check Suction Temperature Sensor

 

6.

Compare board sensor reading against

 

 

 

 

 

 

 

 

actual suction line temperature.

 

 

 

7.

Check Suction Pressure Transducer

 

7.

Compare pressure reading against gauges.

 

 

 

 

 

 

 

 

 

24

Page 24
Image 24