Expansion Valve Capacity
|
|
|
|
|
|
| |||
|
|
| Evaporator Temperature (°F.) | Evaporator Temperature (°F.) | |||||
|
|
| +20 |
| +20 |
|
| ||
Part Number | Valve | Pressure Drop Across Valve (psi) | Pressure Drop Across Valve (psi) | ||||||
100 | BTUH | 100 | BTUH | 100 | BTUH | 100 | BTUH | ||
29320003 | 0.68 | 8160 | 0.64 | 7680 | 0.48 | 5760 | 0.42 | 5040 | |
29320004 | 3.27 | 39240 | 3.07 | 36840 | 2.31 | 27720 | 2.05 | 24600 | |
29320007 - 08 | 8.02 | 96240 | 7.54 | 90480 | 5.65 | 67800 | 5.01 | 60120 | |
29320013 | 15.14 | 181680 | 14.25 | 171000 | 10.69 | 128280 | 9.47 | 113640 | |
29320014 | 22.18 | 266160 | 20.87 | 250440 | 15.65 | 187800 | 13.86 | 166320 |
Diagnostics
Beacon II Troubleshooting Guide
PROBLEM | Step | ACTION ITEM | IF OK | IF NOT OK | ||||
|
| 1. | Check Primary Power Supply Disconnect |
| 1. | Check fuses and circuit breakers | ||
|
| 2. | Check Voltage to Evaporator Transformer | Go to | 2. | Check field wiring for breaks | ||
LED is not lit. | 3. | Check Transformer Secondary Output Volts | next step | 3. | Replace if necessary | |||
|
| 4. | Check Voltage at Control Board (24V and C) |
| 4. | Check factory wiring and connections | ||
|
| 5. | Replace Control Board |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| 1. | Check Compressor internal overloads |
| 1. | Wait for reset | ||
LED shows Coo, but | 2. | Check Control Power to Condensing Unit |
| 2. | Check transformer voltage (secondary and | |||
|
|
| (24 Volts across “COMP” and “C” at board) | Go to |
| primary) and wiring of 208V power taps. | ||
compressor will not run. | 3. | Check Compressor Contactor Coil Voltage | next step | 3. | Check internal condensing unit wiring | |||
|
| 4. | Check Compressor Contactor “pulled in” |
| 4. | Replace as needed | ||
|
|
|
|
|
|
|
|
|
ERROR CODES: |
|
|
|
|
|
|
| |
E1 Room Sensor |
|
|
| Check Sensor and Board Connection |
| Replace as needed | ||
E2 Defrost Sensor |
|
|
| Check Sensor and Board Connection |
| Replace as needed | ||
E3 Suction Sensor |
|
|
| Check Sensor and Board Connection |
| Replace as needed | ||
E4 Suction Transducer |
|
|
| Check Transducer and Board Connection |
| Replace as needed | ||
E5 Outdoor Sensor |
|
|
| Check Sensor, wiring and Board Connection |
| Replace or remove | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1. | Check Refrigerant Type |
| 1. | Compare board setpoint and refrigerant | |
|
|
| 2. | Check coil for ice |
| 2. | Defrost coil and check defrost cycle | |
|
|
|
|
|
|
|
| settings/setpoints, defrost sensor and |
E6 Low Superheat |
|
|
|
|
|
|
| heater amps. |
|
| 3. | Check Control Board step position from board LED |
| 3. Replace board if EEV steps not at 2. | |||
|
|
| ||||||
During Cooling |
| 4. | Check Electric Expansion Valve Closure | Go to | 4. | Pumpdown system see if LPS opens or if it | ||
(0°F for 2 minutes) |
|
|
|
| next step |
| times out (EEV is bad or LPS is set | |
|
|
|
|
|
|
|
| incorrectly, if times out) – See Pumpdown. |
|
|
| 5. | Compressor Not Operating |
| 5. | Check overloads and contactor. | |
|
|
| 6. | Check Suction Temperature Sensor |
| 6. | Compare board sensor reading against | |
|
|
|
|
|
|
|
| actual suction line temperature. |
|
|
| 7. | Check Suction Pressure Transducer |
| 7. | Compare pressure reading against gauges. | |
|
|
|
|
|
|
|
|
|