Heatcraft Refrigeration Products H-IM-79E Diagnostics, Beacon II Troubleshooting Guide continued

Models: H-IM-79E

1 36
Download 36 pages 38.25 Kb
Page 26
Image 26
Manual background

Diagnostics

Beacon II Troubleshooting Guide (continued)

PROBLEM

Step

ACTION ITEM

IF OK

IF NOT OK

E9 Multi-out to Multi-in

1.

Check for 24 volts power to the board

 

1.

If no voltage, see “LED is not lit” above

Communication Wiring

2.

Check for crossed communication wiring

Go to

2.

for low voltage, see “88888 LED display”

(only shows after initial

Correct wiring from “Master” unit Multi-out

successful connection)

 

(multi-out not wired to multi-in terminals)

next step

 

to Multi-in of “Slave” unit, etc. to all Slaves

 

3.

Check for broken communication wiring

 

3.

and return to Master. (See wiring diagrams)

 

 

Correct wiring between first Slave with

 

 

 

 

 

error to previous board in the sequence.

(E9 continued) Communication Error Occurrence:

Break in the designated lines will cause errors as follows:

 

Master

 

 

 

 

Slave 1

 

 

 

 

Slave 2

 

 

 

 

Slave 3

 

in

out

 

 

 

 

 

in

out

 

 

 

 

 

in

out

 

 

 

 

 

in

out

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line #

Master

1E9

2E9

3E9

4E9

Slave1

E9

no error no error no error

Beacon II Smart

Controller

in out

Master

in out

Slave 2

E9

E9

no error no error

Slave 1

in out

Slave 2

in out

Slave 3

E9

E9

E9

no error

Slave 3

in out

[With Beacon II Smart Controller]

Line #

SMART

1+COMM+

2+COMM+

3+COMM+

4+COMM+

5 +COMM+

Manual background 1 Manual backgroundManual background 2

5

Master

Slave1

E9

no error

no error

E9

no error

no error

no error

no error

no error

no error

34

Slave 2

Slave 3

no error

no error

E9

E9

E9

E9

no error

E9

no error

no error

PROBLEM

Step

ACTION ITEM

IF OK

IF NOT OK

 

888 LED display

 

 

 

 

 

 

 

1.

Check Voltage to Evaporator Transformer

 

1.

Check field wiring for breaks or shorts

 

(power is below 18V and

 

2.

Check Transformer Secondary Output Volts

Go to

2.

Replace if necessary

 

appears at initial power)

 

3.

Check Voltage at Control Board (24 and C)

next step

3.

Check factory wiring and connections

 

 

 

4.

Check Voltage at Beacon II Smart Controller

 

4.

Check field wiring from board

 

 

 

 

 

 

 

 

 

LED displays dLy

1.

Check for low voltage

 

1.

Check all steps for “888 LED display”

 

 

 

 

Go to

 

Voltage could drop off too fast to show.

 

then oFF with no

 

2.

Check for short in field wiring from “comp” on

next step.

2.

Check internal factory wiring to

 

displayed errors

 

 

board to condensing unit terminal connection

 

 

compressor contactor.

 

 

 

3.

Replace defective contactor (holding coil)

 

 

 

 

 

 

 

 

 

 

 

 

26

Page 26
Image 26
Heatcraft Refrigeration Products H-IM-79E manual Diagnostics, Beacon II Troubleshooting Guide continued, Problem