Programming & Reviewing
Programming And Reviewing Settings/Changes (Cont’d.)
Use this button to “CLEAR/TEST”
Pressing this button ONCE will return the LED display to
the default display. With the system in the OFF mode, pressing and holding this button will start the “TEST” mode. In the “TEST” mode it will cycle through each output for 10 seconds. The display will only show “tst”
during “TEST” mode. Test mode will automatically terminate after 3 sequences.
Locking The Beacon II Board
The Beacon II board is lockable to prevent programmed setting changes by unauthorized personnel. When
locked, the program setpoints cannot be changed. To lock the setting:
•Press “PROGRAM REVIEW” button.
•Press and hold “MONITOR” button.
•While holding “MONITOR” button, press “ENTER” button.
•The LCD will display Loc.
This will prevent unauthorized personnel program changes. To unlock, repeat steps above. LCD will display “UnL”.
STATUS INDICATOR LED
A RED,
•OFF
All Evaporators
•COOLING
Single Evaporator- Multiple Evaporators
Master Evap - Slave Evaps -
•Pumpdown
All Evaporators
•DEFROST
All Evaporators
•TEST
All Evaporators
•SERVICE
All Evaporators
•ALARMS
Box Temp / oFF
Box Temp /Coo
Box Temp / Coo
Coo
Pdn
dEF
tSt
SEr
A1
A2
A3
A4
Box Temperature/ Mode is displayed
Box Temperature/ Mode is displayed
Box Temperature/ Mode is displayed Operating Mode is displayed
High Box Temp Low Box temp System
Compressor pumps down and tries to restart after 4 minutes.
Input Fault
Box Temp., Suction Temp., Pressure Transducer open or not installed
15