Service Record

Service Record

Date of Start-up

Location Address

CONDENSING UNIT

MODEL #

SERIAL #

COOLER UNIT

MODEL #

SERIAL #

FREEZER UNIT

MODEL #

SERIAL #

ELECTRICAL

Check Primary Supply voltage.

If 208 V, change transformer wiring in the Cooler and Freezer to the 208 V tap

YES

Check Compressor Amps for COOLER and FREEZER compressors. Should match nameplate.

YES NO

PIPING

• Is suction line trapped at the Cooler?

YES NO

• Is suction line trapped at the Freezer?

YES NO

DRAIN LINES

• Are drain lines sloped properly?

YES NO

• Is drain line trapped outside the Cooler?

YES NO

• Is drain line trapped outside the Freezer?

YES NO

Is heat tape wrapped along entire length of the drain line in the Freezer?

YES NO

Is heat tape plugged in and heating the drain line?

YES NO

INSULATION

• Are Liquid lines fully insulated?

YES NO

• Are Suction lines fully insulated?

YES NO

SETTINGS

Check Beacon II board settings for the

following:

FREEZER

Refrigerant Type

R404A

Box Setpoint Temp.

-10°F.

Superheat

8°F.

No. of Defrost / Day

4

Defrost End Temp.

65°F.

COOLER

 

Refrigerant Type

R22

Box Setpoint Temp.

35°F.

Superheat

8°F.

No. of Defrost/Day

2

Defrost End Temp.

50°F.

SYSTEM CHECKS

Check Compressor Superheat for the COOLER (Should be between 20°F. & 30°F.)

YES NO

Check Compressor Superheat for the FREEZER (Should be between 20°F. & 30°F.)

YES NO

Force unit into a Defrost Check heater amps. Should match nameplate amps.

YES NO

Check LPS Time Delay Relays. Should be set at 1 minute for both the COOLER and

FREEZER.

YES NO

Check Low Pressure Switch on FREEZER. Should be set at 0 psig Cut-out/10 psig Cut-in.

YES NO

Did FREEZER and COOLER cycle off on LPS at Setpoint Temperature?

YES NO

• Is the sight glass free of bubbles?

YES NO

Are the COOLER and FREEZER fans at proper speeds?

YES NO

Check system for refrigerant leaks. Are there any leaks on the COOLER, FREEZER, CONDENSING UNIT or INTERCONNECTING PIPING?

YES NO

Check system piping for unusual vibration or noise. Is there any unusual vibration or noise on the COOLER, FREEZER, CONDENSING UNIT or

INTERCONNECTING PIPING?

YES NO

Start the FREEZER only. Does the compressor start and evaporator fans run for this FREEZER?

YES NO

35