Heatcraft Refrigeration Products H-IM-79E Status Indicator LED, Low Ambient Operation, Pumpdown

Models: H-IM-79E

1 36
Download 36 pages 38.25 Kb
Page 16
Image 16
Status Indicator LED

 

 

 

 

 

 

 

 

 

 

 

 

Status Indicator LED

 

 

 

 

STATUS INDICATOR LED

 

 

ERRORS

E 1

-

Room temperature sensor shorted, open or not installed

 

 

 

 

E 2

-

Defrost temperature sensor shorted, open or not installed

 

 

 

 

E 3

-

Suction temperature sensor shorted, open or not installed

 

 

 

 

E 4

-

Suction pressure transducer shorted, open or not installed

 

 

 

 

E 5

-

Outdoor temperature sensor shorted

 

 

 

 

E 6

-

Low superheat during cooling

 

 

 

 

E 7

-

Compressor shutdown

 

 

 

 

E 9

-

(high or low refrigerant pressure or low oil pressure)

 

 

 

 

Multi-in/Multi-out wiring error

 

 

 

 

 

 

 

 

OTHERS

Coo -

Room Temperature sensor open or not connected

 

 

 

 

Loc -

(Instead of displaying box temperature)

 

 

 

 

Board is locked. Settings cannot be changed

 

 

 

 

UnL -

Unlock the board settings

 

 

 

 

 

 

 

 

Low Ambient Operation

All units are shipped standard with Head Master valves. (Scroll compressor units have a 100 PSI Head Master

valve and all other systems have a 180 PSI head master valve.) Condensing units with multiple condenser fans will have one or more fans cycle on Pressure Fan Cycling

switch.

An adjustable Time Delay relay, factory set at 1 minute, is wired across the Low Pressure switch (LPS). In cold ambient this allows time for the suction pressure to build up and prevent nuisance tripping of the LPS.

Pumpdown

When any of these three conditions occurs the compressor will turn off and not restart until there is a call for cooling or a periodic pumpdown.

Periodic Pumpdown

While in the OFF cycle, if there isn’t a call for cooling (Box setpoint temperature is met) but:

The evaporator suction pressure has risen to 10 psig

The low pressure switch has closed

At the end of each cooling cycle, when the box temperature is met, the Beacon system will pump down and shut off the compressor.

To pumpdown, the EEV closes and the compressor runs until one of the following occurs:

The low pressure switch opens

The suction pressure at the evaporator is 4 psig

A total of two minutes has elapsed

The system will initiate pumpdown. This periodic pumpdown will occur at 4 minute intervals when these two conditions are met.

16

Page 16
Image 16