At initial power up, each Beacon II board checks for system errors. The system error check involves checking the various temperature sensors to determine whether any of these sensors are shorted or open.

The system will pumpdown and cycle off and will not restart until the fault is cleared or the circuit breaker reset, for the following conditions:

-Suction sensor shorted, open or not installed

-Room temperature sensor shorted or not installed

-Pressure Transducer open or not installed

The system will pumpdown, cycle off and try to restart for these faults. Each try will be after the 4 minutes “Hold Off” period, for the following fault conditions:

-High pressure or low pressure cutout

-Oil pressure

After the fourth try, the Alarm contacts will be closed and an alarm message displayed on the LED. To clear

this condition, the system should be cycled through the “SERVICE MODE” after the correction is completed.

Evaporator Fans Shut Off

In some installations, it is desirable to shut off the evaporator fans periodically. This is easily accomplished

on Beacon II by wiring a single pole, single throw switch (SPST) between the terminals marked “SERVICE” and “COM” on the Beacon II board. Closing this switch will

cause the system to pumpdown and shut off.

ERROR CODES

E1 - Room temperature sensor shorted, open or not installed

E2 - Defrost temperature sensor shorted, open or not installed

E3 - Suction temperature sensor shorted, open or not installed

E4 - Suction pressure transducer shorted, open or not installed

E5 - Outdoor temperature sensor shorted

E6 - Low superheat

E7 - Compressor shut down

(high or low pressure switch open or oil pressure switch open)

E9 - Multi-in/multi-out wiring error

Air Defrost fan motors must be wired through the fan relay on the Beacon II board for this to be effective on Air Defrost systems. The entire system will be shut off and remain off until the SPST switch is opened.

Air Defrost evaporator fans are setup to run constantly. If there is a need to shut down the evaporator fans on an Air Defrost system, this can be accomplished by wiring the evaporator fan motor or evaporator fan motor contactor through the fan relay on the Beacon II board.

When this is done and the Air Defrost system is placed in “SERVICE,” the evaporator fans will shut off when the system is in pumpdown.