Single System With Multiple Evaporators
•Check all wiring connections to be sure they are correct and tight.
•On the condensing unit
-Check the setting of time delay relay. It should be set at 1 minute (the second marker).
-Check the low pressure switch setting on freezer units. It must be set to 0 psig
•Turn power on.
•On the MASTER evaporator
-DO NOT REMOVE the room sensor from any evaporator
-Use the “PROGRAM REVIEW” button to scroll through settings.
-Check “rEF” (Refrigerant Type). Factory defaults are: air defrost
Change to the refrigerant being used.
-Check “bot” (Box Temperature). Factory defaults are: air defrost 35°F and electric defrost
Change to the desired temperature.
-Review and change other setting if necessary.
-See procedures below on how to change settings.
•On the SLAVE evaporators. All Beacon II boards are shipped with the factory default as a “MASTER” evaporator.
-DO NOT REMOVE the Room Sensor from any evaporator
-Each SLAVE Evaporator must be
changed to identify it as a SLAVE. Use the “PROGRAM REVIEW” button to scroll until “SLA” appears, then use the “SELECT” knob to select
“YES” then press “ENTER.”
CU
M
|
|
|
|
|
|
|
|
|
|
| S |
|
| S |
| ||
|
|
|
|
|
|
|
|
|
S
M = Master Evaporator
S = Slave Evaporator
CU = Condensing Unit
9