Preventive Maintenance

EVAPORATORS

All evaporator units should be checked once a month or more often for proper defrosting because the amount and pattern of frosting can vary greatly. It is dependent on the coil temperature, the temperature of the room, the type of product being stored, how often new product is brought into the room and the percentage of time the door to the room is open. It may be necessary to periodically change the number of defrost cycles or adjust the duration of defrost.

CONDENSING UNITS / EVAPORATORS

Under normal usage conditions, maintenance should cover the following items at least once every 6 months:

1.Check and tighten ALL electrical connections

2.Check all wiring and insulators

3.Check contactors for proper operation and for worn contact points

4.Check all fan motors. Tighten motor mount bolts and nuts and tighten fan set screws

5.Clean the condenser coil surface

6.Check the refrigerant and oil level in the system

7.Check the operation of the control system. Make certain all safety controls are operating properly

8.Check that all defrost controls are functioning properly

9.Clean the evaporator coil surface

10.Clean the drain pan and check the drain pan and drain line for proper drainage

11.Check the drain line heater for proper operation, cuts and abrasions

12.Check and tighten all flare connections

Check-Out & Start-Up

After the installation has been completed, the following points should be covered before the system is placed in operation:

(a)Check all electrical and refrigerant connections. Be sure they are all correct and tight.

(b)Check voltage taps on transformer. The transformer is shipped wired to 240 voltage tap/connection. If your supply voltage is 208 volt systems, change to 208 voltage tap.

(c)Check setting of time delay relay for low pressure switch in condensing unit. It should be set at one minutes (the second marker).

(d)Check high and low pressure controls, pressure regulating valves, oil pressure safety controls, and all other safety controls and adjust them, if necessary.

(e)On freezers only, check the low pressure switch setting. It must be set to 0 PSIG cut out, 10 PSIG cut in, to allow start and operation, especially in cold ambients.

(f) Liquid line should always be insulated.

(g)Wiring diagrams, instruction bulletins, etc. attached to the condensing units should be read and filed for future reference.

(h)All fan motors on air cooled condensers, evaporators, etc. should be checked for proper rotation. Fan motor mounts should be carefully checked for tightness and proper alignment.

(i)Observe system pressures during charging and initial operation. Do not add oil while the system is short of refrigerant unless oil level is dangerously low.

(j)Continue charging until system has sufficient refrigerant for proper operation. Do not overcharge. Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant.

(k)Do not leave unit unattended until the system has reached normal operating conditions and the oil charge has been properly adjusted to maintain the oil level at the center of the sight glass.

(l)At initial start-up, the system may cycle off at 2 minutes and display a low superheat error, then restart itself. This cycle may be repeated a few times. Do not shut the system off. Let the system run, as it may take a few cycles for the electric expansion valve to attain the correct setting for the desired superheat.

CAUTION: Extreme care must be taken in starting compressors for the first time after system charging. At this time, all of the oil and most of the refrigerant might be in the compressor creating a condition which could cause compressor damage due to slugging. Activating the crankcase heater for 24 hours prior to start-up is recommended. If no crankcase heater is present, then directing a 500 watt heat lamp or other safe heat source on the lower shell of the compressor for approximately thirty minutes will be beneficial in eliminating this condition which might never reoccur.

34

Page 34
Image 34
Heatcraft Refrigeration Products H-IM-79E manual Preventive Maintenance, Evaporators

H-IM-79E specifications

Heatcraft Refrigeration Products has long been a leader in eco-friendly and efficient cooling solutions, and the H-IM-79E is a prime example of their commitment to innovation and sustainability. Designed for commercial use, the H-IM-79E is a high-performance refrigeration unit ideal for supermarkets, convenience stores, and restaurants, where reliable temperature control is essential.

One of the standout features of the H-IM-79E is its energy efficiency. This unit employs advanced compressor technology that optimizes power consumption without sacrificing cooling performance. In addition, it is designed to minimize operational costs, making it an attractive option for businesses looking to reduce their energy bills while maintaining high standards of refrigeration.

The H-IM-79E integrates a robust refrigerant management system that uses environmentally friendly refrigerants, aligning with Heatcraft's commitment to reducing the carbon footprint of their products. This not only helps businesses comply with environmental regulations but also promotes a healthier planet for future generations.

Another key characteristic of the H-IM-79E is its superior temperature stability. The unit is equipped with precision temperature control technology that ensures consistent cooling performance, preventing temperature fluctuations that can compromise food quality and safety. This reliability is crucial in commercial settings where maintaining optimal storage conditions is essential.

The design of the H-IM-79E is also noteworthy. It features a compact footprint, allowing it to fit seamlessly into various commercial environments without taking up valuable floor space. Additionally, the unit is built with durable materials, ensuring longevity and minimizing maintenance needs.

User-friendly interfaces make the H-IM-79E easy to operate. It includes advanced monitoring and diagnostics capabilities, allowing business owners to track performance in real-time and address potential issues before they escalate. The incorporation of smart technologies means that operators can remotely monitor and control the system, providing flexibility and peace of mind.

In summary, the Heatcraft Refrigeration Products H-IM-79E stands out for its energy efficiency, eco-friendly refrigerant use, reliable temperature control, compact design, and user-friendly features. This combination of attributes makes it an ideal choice for businesses that prioritize both sustainability and performance in their refrigeration needs.