Heatcraft Refrigeration Products H-IM-79E Checking Operation of Expansion Valve, A• •C •• B D

Models: H-IM-79E

1 36
Download 36 pages 38.25 Kb
Page 20
Image 20
Checking Operation of Expansion Valve

Checking Operation of Expansion Valve

Checking Operation Of Expansion Valve (EEV)

To check if the expansion valve is closing properly:

Install a pressure gauge-set to suction line at the condensing unit. With the system running, close the valve on the liquid line, at the con densing unit. The system should pumpdown and shut off on the Low Pressure switch (LPS). If the system does not pumpdown and trip on the LPS then the compressor valves are weak and needs to be changed.

After the system pumps-down and trip on the LPS, put the system in the service mode. This will cause the Expansion valve to close. Open the valve on the liquid line, at the condensing unit. The suction pressure reading on the gauge set should not increase. If the suction pressure increases then the expansion valve is leaking and should be changed.

The Expansion valve position can be monitored from the LED display pressing the “MONITOR” button and scrolling to ESP. This will indicate the number of steps the valve is open.

This can also be checked by using the EXV test pins on the board. This is indicated by a 0 to 5 Volts DC signal. At 0 Volt the valve is closed and at 5 Volts the valve is fully open. At values between 0 and 5 Volt, the valve will be opened proportionately.

Use the “MONITOR” button to display “SCP”” Evaporator Suction Pressure. Record the pressure displayed. Start the system and observe the pressure displayed. If the pressure does not increase, the expansion valve could be defective.

If the system is running, use the “MONITOR” button to display “SCP” Evaporator Suction Pressure. Record the pressure displayed. While the system is running, press the “FORCE SERVICE” button. Observe the pressure while the system is pumping down. The pressure should decrease. If it does not, this indicates a defective valve.

Expansion Valve Motor Winding Resistance

If the expansion valve is suspected of not functioning properly the motor windings resistance should be measured. This is a bipolar motor with two windings. Measure the resistance at the pins, on top of the valve, between locations A and B

or C and D.

(Note that the pins are not labeled A, B, C, D. This labeling is just for reference. Also, two of the pins, at location B and location D, have a wider spacing between them than between location A and C)

Expansion Valve

A• •C

Checking Operation Of Expansion Valve (EEV)

B D

Motor Winding

Pins

For valve size 29320003 and 2930004, the resistance measured between pin locations A and B or C and D should be approximately 336 Ohms when valve is at 75ºF.

For valve size 2930007, 29320008, 29320013 and 29320014, the resistance measured between pin locations A and B or C and D should be approximately 116 Ohms when the valve is at 75ºF.

Continues to Page 21

20

Page 20
Image 20
Heatcraft Refrigeration Products H-IM-79E Checking Operation of Expansion Valve, Checking Operation Of Expansion Valve EEV