System Defaults
Table 1. Resistance/Temperature Specification |
| |||
| Temperature °F | Ohms | Temperature °F | Ohms |
| 104 | 5,320 | 32 | 32,650 |
| 86 | 8,060 | 23 | 42,330 |
| 77 | 10,000 | 14 | 55,330 |
| 68 | 12,490 | 5 | 72,950 |
| 59 | 15,710 | 97,070 | |
| 50 | 19,900 | 130,410 | |
| 41 | 25,400 | 176,960 |
Table 2. System Defaults |
|
|
|
PARAMETERS | CODE | AIR | ELECTRIC |
Refrigerant | rEF | ||
Box Temperature | bot | 35°F | |
Superheat | SUP | 8°F | 8°F |
Slave Evaporator | SLA | No | No |
No. of Defrost per Day | dFn | 2 | 4 |
Defrost | dFF | 40 min. | 30 min. |
Defrost End Temperature | dFt | 45°F | 60°F |
Defrost Delay Start Time | dFS | 0 hrs. | 0 hrs. |
Alarm High Temperature | ALH | 50°F | 5°F |
Alarm Low Temperature | ALL | 30°F | |
Alarm Time | ALt | 60 min. | 60 min. |
Temperature Units | °F | °F |