Frequency-related Functions

Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will
apply regardless of the source of the
speed reference. You can configure the
lower frequency limit to be greater than
zero as shown in the graph. The upper
limit must not exceed the rating of the
motor or capability of the machinery.
The maximum frequency setting
(A004/A204) takes precedence over
frequency upper limit (A061/A261).
“A”Function Defaults
Func.
Code
Name/
SRWDisplay Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)Units
Frequency upper limit settingA061
Lim H 0000.0Hz
Sets a limit on output frequency
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
U0.0 0.0 Hz
Frequency upper limit
setting, 2nd motor
A261
2Lim H 0000.0Hz
Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
U0.0 0.0 Hz
Frequency lower limit settingA062
Lim L 0000.0Hz
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
U0.0 0.0 Hz
Frequency lower limit
setting, 2nd motor
A262
2Lim L 0000.0Hz
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
U0.0 0.0 Hz
Output
frequency
A061 Upper
limit
Settable
range
A062 Lower
limit
Frequency command
0

320

Configuring Drive
Parameters
3 20