“C”Function Defaults
Func.
Code
Name/
SRWDisplay Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)Units
Overload level settingC041
OV LVL 001.60A
Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)
U
Rated current
for each
inverter model
A
Overload level setting,
2nd motor
C241
2OV LVL 001.60A
Sets the overload signal level
between 0% and 200% (from 0 to
two time the rated current of the
inverter)
U
Rated current
for each
inverter model
A
Frequency arrival setting
for acceleration
C042
ARV ACC 0000.0Hz
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
U0.0 0.0 Hz
Frequency arrival setting
for deceleration
C043
ARV DEC 0000.0Hz
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
U0.0 0.0 Hz
PID deviation level settingC044
ARV PID 003.0%
Sets the allowable PID loop error
magnitude (absolute value), SP-PV,
range is 0.0 to 100%
U3.0 3.0 %
PID FBV function high
limit
C052
PID LtU 0100.0%
When the PV exceeds this value,
the PID loop turns OFF the PID
second stage output, range is 0.0 to
100%
U100.0 100.0 %
PID FBV function variable
low limit
C053
PID LtL 0000.0%
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U0.0 0.0 %