Second Acceleration and Deceleration Functions

The X200 inverter features two-stage acceleration and deceleration ramps. This givesflexibility in the profile shape. You can specify the frequency transition point, the pointat which the standard acceleration (F002) or deceleration (F003) changes to the secondacceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] totrigger this transition. These profile options are also available for the second motorsettings. Select a transition method via A094 as depicted below. Be careful not toconfuse the
second acceleration/deceleration settings
with settings for the
second motor
!
“A”Function Defaults
Func.
Code
Name/
SRWDisplay Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)Units
Acceleration (2) time settingA092
ACC 2 0015.00s
Duration of 2nd segment of
acceleration, range is:
0.01 to 3000 sec.
915.00 15.00 sec
Acceleration (2) time setting,
2nd motor
A292
2ACC2 0015.00s
Duration of 2nd segment of
acceleration, 2nd motor, range is:
0.01 to 3000 sec.
915.00 15.00 sec
Deceleration (2) time settingA093
DEC 2 0015.00s
Duration of 2nd segment of
deceleration, range is:
0.01 to 3000 sec.
915.00 15.00 sec
Deceleration (2) time setting,
2nd motor
A293
2DEC2 0015.00s
Duration of 2nd segment of
deceleration, 2nd motor, range is:
0.01 to 3000 sec.
915.00 15.00 sec
Select method to switch to
Acc2/Dec2 profile
A094
ACC CHG TM
Two options for switching from
1st to 2nd accel/decel:
00}2CH input from terminal
01}Transition frequency
U00 00
Select method to switch to
Acc2/Dec2 profile, 2nd motor
A294
2ACCCHG TM
Two options for switching from
1st to 2nd accel/decel:
00}2CH input from terminal
01}Transition frequency
(2nd motor)
U00 00
A094 = 00 Transition via 2CH input
Output
frequency
A
ccel 1
A
ccel 2
2CH
input
1
0
t
t
0
A094 = 01 Transition via freq. level
Output
frequency
A
ccel 1
A
ccel 2
t
0
A095 Frequency
transition point

325

Configuring Drive
Parameters
3 25
&RQ¿JXULQJ'ULYH
Parameters