Jogging Command

The Jog input [JG] is used to command
the motor to rotate slowly in small
increments for manual operation. The
speed is limited to 10 Hz. The
frequency for the jogging operation is
set by parameter A038. Jogging does
not use an acceleration ramp, so we
recommend setting the jogging
frequency A038 to 5 Hz or less to
prevent tripping.
When the terminal [JG] is turned ON
and the Run command is issued, the
inverter outputs the programmed jog
frequency to the motor. To enable the
Run key on the digital operator for jog
input, set the value 01 (terminal mode)
in A002 (Run command source).
The type of deceleration used to end a motor jog operation is selectable by programming
function A039. The options are:
• 00 Free-run stop (coasting)
• 01 Deceleration (normal level) and stop
• 02 Use DC braking and stop
Option
Code
Terminal
Symbol FunctionName State Description
ON Inverter is in Run Mode, output to motor runs at
jog parameter frequency
06 JG Jogging
OFF Inverter is in Stop Mode
Validfor inputs:C001~C005
Requiredsettings A002=01, A038>B082,
A038>0, A039
Notes:
xNo jogging operation is performed when the set
value of jogging frequency A038 is smaller than
the start frequency B082, or the value is 0Hz.
xBe sure to stop the motor when switching the
function[JG] ON or OFF.
Example (requires input configuration—see
page 3–49):
See I/O specs on page 4–6.
54321L
PCS P24
JG
[JG] 1
0
[FW],
[RV] 1
0
Jog
speed
A038
Jog decel type
A039

414

Operations and
Monitoring
4 14