Action Display Func./Parameter
(Starting point) A003 Base frequency setting
Press the key and hold until Æ A082 AVR voltage select
Press the key.
230
or
400
Default value for AVR voltage:
200V class = 230VAC
400V class = 400VAC (HFE)
= 460VAC (HFU)
Press the or key as needed. 215 Set to your motor specs (your display
may be different)
Press the key. A082 Store parameter, returns to “A”
Group list

Setthe Motor Current – The inverter has thermal overload protection that is designed

to protect the inverter and motor from overheating due to an excessive load. The

inverter’s uses the motor’s current rating to calculate the time-based heating effect.

This protection depends on using correct current rating for your motor. The level of

electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the

inverter’s rated current. A proper configuration will also help prevent unnecessary

inverter trip events.

Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps

below to configure the inverter’s overload protection setting.

Action Display Func./Parameter
(Starting point) A082 AVR voltage select
Press the key. A- - - “A” Group selected
Press the key. b- - - “B” Group selected
Press the key. b001 First “B” Group parameter selected
Press the key and hold until Æ b012 Level of electronic thermal setting
Press the key. 1.60 Default value will be 100% of
inverter rated current
Press the or key as needed. 1.80 Set to your motor specs (your display
may be different)
Press the key. b012 Store parameter, returns to “B”
Group list
FUNC
STR
1
12
FUNC
1
FUNC
1
12
FUNC
STR

232

Inverter Mounting
and installation
2 32
Inverter Mountingand
installation