Run Command Source Setting – For parameter A002, the following table provides a
further description of each option, and a reference to other page(s) for more information.
Code RunCommand Source Refer to page(s)…
01 Control terminal – The [FW] or [RV] input terminals control
Run/Stop operation
4-11
02 Keypad Run key – The Run and Stop keys provide control 2-24
03 ModBus network input – The network has a dedicated coil
for Run/Stop command and a coil for FW/RV
B-19
A001/A002Override Sources – The inverter allows some sources to override the setting
for output frequency and Run command in A001 and A002. This provides flexibility for
applications that occasionally need to use a different source, leaving the standard
settings in A001/A002.
The inverter has other control sources that can temporarily override the parameter
A001 setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority (“1” is the highest priority).
Priority A001Frequency Source Setting Method Referto page…
1 [CF1] to [CF4] Multi-speed terminals 4-12
2 [OPE] Operator Control intelligent input 4-29
3 [F-TM] intelligent input 4-31
4 [AT] terminal 4-22
5 A001 Frequency source setting 3-10
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority (“1” is the highest priority).
Priority A002Run Command Setting Method Referto page…
1 [OPE] Operator Control intelligent input 4-29
2 [F-TM] intelligent input 4-31
3 A002 Run command source setting 3-10