Set Second Motor, Special Set

If you assign the [SET] function to an intelligent input terminal, you can select between
two sets of motor parameters. The second parameters store an alternate set of motor
characteristics. When the terminal [SET] is turned ON, the inverter will use the second
set of parameters to generate the frequency output to the motor. When changing the
state of the [SET] input terminal, the change will not take effect until the inverter is
stopped. Special Set [SP-SET] is for changing the second motor parameters without
stopping the motor. However the changeable parameters are limited.
When you turn ON the [SET] input, the inverter operates per the second set of
parameters. When the terminal is turned OFF, the output function returns to the
original settings (first set of motor parameters). Refer to “Configuring the Inverter for
Multiple Motors” on page 4–58for details.
Parameters SET SP-SET Parameters SET SP-SET
F002/F202 99
A093/A293 99
F003/F203 99
A094/A294 99
A001/A201 9-A095/A295 99
A002/A202 9-A096/A296 99
A003/A203 9-b012/b212 9-
A004/A204 9-b013/b213 9-
A020/A220 99
b021/b221 9-
A041/A241 9-b022/b222 9-
A042/A242 99
b023/b223 9-
A043/A243 99
b028/b228 9-
A044/A244 9-
A045/A245 9-
C001~C005/
C201~C205 9-
A061/A261 99
C041/C241 9-
A062/A262 99
H003/H203 9-
A092/A292 99
H004/H204 9-
H006/H206 9-
Option
Code
Terminal
Symbol FunctionName State Description
ON causes the inverter to use the 2nd set of motor
parameters for generating the frequency output to
motor
08
53
SET
SP-SET
Set(select) 2nd
Motor data
Set 2nd motor data
Special SET
OFF causes the inverter to use the 1st (main) set of
motor parameters for generating the frequency
output to motor
Validfor inputs:C001~C005
Requiredsettings (none)
Notes:
xIf the terminal state is changed while the
inverter is running, the inverter continues using
the current set of parameters until the inverter
is stopped.
Example (requires input configuration—see
page 3–49):
See I/O specs on page 4–6.
54321L
PCS P24
SET / SP-SET

416