Network Communications Settings

The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
“ModBus Network Communications” on page B-1 for more information on controlling
any monitoring your inverter from a network.
“C”Function Defaults
Func.
Code
Name/
SRWDisplay Description
Run
Mode
Edit
-FE
(EU)
-FU
(USA)Units
Selection of OPE / ModBusC070
PARAM REM
Two option codes:
02}OPE or option
03}ModBus (485)
U02 02
Communication speed
selection
C071
COM BAU 4800
Three option codes:
04}4800 bps
05}9600 bps
06}19200 bps
U06 04 baud
Node allocationC072
COM ADR 00001
Set the address of the inverter on
the network. Range is 1 to 32 U1. 1.
Communication parity
selection
C074
COM PRTY NON
Three option codes:
00}No parity
01}Even parity
02}Odd parity
U00 00
Communication stop bit
selection
C075
COM STP 1BIT
Range is 1 to 2 U11bit
Communication error selectC076
COM ESlct None
Selects inverter response to
communications error.
Five options:
00}Trip (Error code E60)
01}Decelerate to a stop and trip
(Error code E60)
02}Disable
03}Free run stop (coasting)
04}Decelerate to a stop
U02 02
Communication error time-
out
C077
COM ETIM 000.00s
Sets the communications watchdog
timer period.
Range is 0.00 to 99.99 sec
U0.00 0.00 sec.
Communication wait timeC078
COM Wait 00000ms
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U0. 0. msec.

360

Configuring Drive
Parameters
3 60