Func.

 

 

Default Value

Set

Name / Description

–FE2 / –FU2 /

Code

Value

 

 

–FR

 

 

 

 

 

 

 

 

 

 

 

 

A021

Multi-speed frequency settings

0.00

 

to

(for both motors)

 

 

 

A035

 

 

 

 

 

 

 

 

 

A038

Jog frequency setting

 

1.00

 

 

 

 

 

 

A039

Jog stop mode

 

00

 

 

• 00 Free-run stop, jogging disabled during

 

 

 

motor run

 

 

 

 

• 01 Controlled deceleration, jogging

 

 

 

disabled during motor run

 

 

 

• 02 DC braking to stop, jogging disabled

 

 

 

during motor run

 

 

 

 

• 03 Free-run stop, jogging always enabled

 

 

 

• 04 Controlled deceleration, jogging

 

 

 

always enabled

 

 

 

 

• 05 DC braking to stop, jogging always

 

 

 

enabled

 

 

 

 

 

 

 

A041/

Torque boost method selection

00

 

A241

• 00 Manual torque boost

 

 

 

• 01 Automatic torque boost

 

 

 

 

 

 

A042/

Manual torque boost value

1.0

 

A242

 

 

 

 

 

 

 

 

A043/

Manual torque boost frequency adjustment

5.0

 

A243

 

 

 

 

 

 

 

 

A044/

V/f characteristic curve selection

00 / 01 / 00

 

A244

• 00 V/f constant torque

 

 

 

• 01 V/f variable torque

 

 

 

• 02 V/f free-setting curve

 

 

 

 

 

 

 

A045

V/f gain setting

 

100.

 

 

 

 

 

 

A051

DC braking enable

 

00

 

 

• 00 Disable

• 01 Enable

 

 

 

 

 

 

A052

DC braking frequency setting

0.50

 

 

 

 

 

 

A053

DC braking wait time

 

0.0

 

 

 

 

 

A054

DC braking force during deceleration

0.

 

 

 

 

 

A055

DC braking time for deceleration

0.0

 

 

 

 

 

A056

DC braking / edge or level detection for

01

 

 

[DB] input

 

 

 

 

 

 

 

A057

DC braking force for starting

0.

 

 

 

 

 

A058

DC braking time for starting

0.0

 

 

 

 

 

A059

DC braking carrier frequency setting

3.0

 

 

 

 

 

A061/

Frequency upper limit setting

0.00

 

A261

 

 

 

 

 

 

 

 

 

16