“b” Group: Fine-tuning Functions
Func. |
|
| Default Value | Set | |
Name / Description | |||||
Code | Value | ||||
|
| ||||
|
|
|
| ||
|
|
|
| ||
|
|
|
| ||
b001 | Selection of automatic restart mode | 00 |
| ||
| • 00 Alarm output after trip, automatic |
|
| ||
| restart disabled |
|
|
| |
| • 01 Restart at 0Hz |
|
|
| |
| • 02 Resume operation after frequency |
|
| ||
| matching |
|
|
| |
| • 03 Resume previous freq. after freq. |
|
| ||
| matching, then decelerate to stop and |
|
| ||
| display trip info |
|
|
| |
|
|
|
| ||
b002 | Allowable | 1.0 |
| ||
|
|
|
| ||
b003 | Retry wait time before motor restart | 1.0 |
| ||
|
|
|
| ||
b004 | Instantaneous power failure / | 00 |
| ||
| trip alarm enable |
|
|
| |
| • 00 Disable | • 01 Enable |
|
| |
| • 02 Disable during stop and ramp to stop |
|
| ||
|
|
|
| ||
b005 | Number of restarts on power failure / under- | 00 |
| ||
| voltage trip events |
|
|
| |
| • 00 Restart 16 times | • 01 Always restart |
|
| |
|
|
|
| ||
b006 | Phase loss detection enable | 0.00 |
| ||
| • 00 Disable – no trip on phase loss |
|
| ||
| • 01 Enable – trip on phase loss |
|
| ||
|
|
|
| ||
b007 | Restart frequency threshold | 1.0 |
| ||
|
|
|
| ||
b012/ | Level of electronic thermal setting | Rated current |
| ||
b212 |
|
| of each inverter |
| |
|
|
|
| ||
b013/ | Electronic thermal characteristic | 01 / 00 / 00 |
| ||
b213 | • 00 Reduced torque | • 01 Const. torque |
|
| |
| • 02 V/f |
|
|
| |
|
|
|
| ||
b015 | Free setting, electronic thermal freq. (1) | 0. |
| ||
|
|
|
| ||
b016 | Free setting, electronic thermal current (1) | 0.0 |
| ||
|
|
|
| ||
b017 | Free setting, electronic thermal freq. (2) | 0. |
| ||
|
|
|
| ||
b018 | Free setting, electronic thermal current (2) | 0.0 |
| ||
|
|
|
| ||
b019 | Free setting, electronic thermal freq. (3) | 0. |
| ||
|
|
|
| ||
b020 | Free setting, electronic thermal current (3) | 0.0 |
| ||
|
|
|
| ||
b021 | Overload restriction operation mode | 01 |
| ||
| • 00 Disabled |
|
|
| |
| • 01 Enabled for accel and constant speed |
|
| ||
| • 02 Enabled for constant speed only |
|
| ||
|
|
|
|
|
19