Func.

 

 

Default Value

Set

Name / Description

–FE2 / –FU2 /

Code

Value

 

 

–FR

 

 

 

 

 

 

 

 

 

 

 

 

b085

Country code for initialization

01 / 02 / 00

 

 

• 00 Japan version

• 01 Europe version

 

 

 

• 02 US version

• 03 (reserved)

 

 

 

 

 

 

b086

Frequency scaling conversion factor

1.0

 

 

 

 

 

 

b087

STOP key enable

 

00

 

 

• 00 Enable

• 01 Disable

 

 

 

 

 

 

b088

Restart mode after FRS

00

 

 

• 00 Restart from 0Hz

 

 

 

 

• 01 Restart from frequency detected from

 

 

 

actual speed of motor

 

 

 

 

 

 

 

b090

Dynamic braking usage ratio

00

 

 

 

 

 

 

b091

Stop mode selection

 

00

 

 

 

 

 

 

b092

Cooling fan control

 

00

 

 

• 00 Fan always ON

 

 

 

 

• 01 Fan ON during Run, OFF during Stop

 

 

 

 

 

 

b095

Dynamic braking control

00

 

 

• 00 Disable

 

 

 

 

• 01 Enable during RUN only

 

 

 

• 02 Enable always

 

 

 

 

 

 

 

b096

Dynamic braking activation level

360/

 

 

 

 

720

 

 

 

 

 

b098

• Thermistor for thermal protection control

00

 

 

• 00 Disable

 

 

 

 

• 01 Enable – PTC thermistor

 

 

 

• 02 Enable – NTC thermistor

 

 

 

 

 

 

b099

Thermal protection level setting

3000

 

 

 

 

 

b100

Free-setting V/f frequency (1)

0.

 

 

 

 

 

b101

Free-setting V/f voltage (1)

0.0

 

 

 

 

 

b102

Free-setting V/f frequency (2)

0.

 

 

 

 

 

b103

Free-setting V/f voltage (2)

0.0

 

 

 

 

 

b104

Free-setting V/f frequency (3)

0.

 

 

 

 

 

b105

Free-setting V/f voltage (3)

0.0

 

 

 

 

 

b106

Free-setting V/f frequency (4)

0.

 

 

 

 

 

b107

Free-setting V/f voltage (4)

0.0

 

 

 

 

 

b108

Free-setting V/f frequency (5)

0.

 

 

 

 

 

b109

Free-setting V/f voltage (5)

0.0

 

 

 

 

 

b110

Free-setting V/f frequency (6)

0.

 

 

 

 

 

b111

Free-setting V/f voltage (6)

0.0

 

 

 

 

 

 

21