Powerup Test

The Powerup Test procedure uses minimal parameter settings to run the motor. The procedure describes two alternative methods for commanding the inverter: via the inverter keypad, or via the logic terminals.

Check power input and motor output wiring (see page 4 diagram).

If using logic terminals for testing, verify correct wiring on [FW], [CM1], [H], [O], and [L] per the diagram on page 4.

Reverse [RV] input wiring (defaults to terminal [8]) is optional.

Step

Description

Via KeypadVia Logic
Terminals

 

 

 

 

 

 

 

 

 

 

 

1

Set speed command

A001 = 02

A001 = 01,

 

source setting

(keypad / F001)

[H–O–L] input

 

 

 

 

2

Set Run FW command

A002 = 02

A002 = 01,

 

source

(Run key)

[FW] input

 

 

 

 

 

Set Run REV

C008 = 01,

 

command source

 

[RV] input

 

 

 

 

3

Set motor base freq.

A003 = 60

 

 

 

4

Set motor poles

H004 = 4 (default), change only if

 

(2 / 4 / 6 / 8)

your motor is different

 

 

 

5

Set keypad display to

Access d001, press Func key, display

 

monitor freq.

will show 0.00

 

 

 

 

6

Perform safety check

Disconnect load from motor

 

 

 

 

 

 

Check, if setting

Ensure voltage on

 

 

F001 = 0.00Hz

[O]—[L] termi-

 

 

 

nals= 0V

 

 

 

 

7

Run Forward

Press Run key

Turn ON the [FW]

 

command

 

terminal

 

 

 

 

8

Increase speed

Pres (hold) key

Increase voltage

 

 

UP

at [O]

 

 

 

 

9

Decrease speed

Pres (hold) key

Decrease voltage

 

 

DOWN

at [O]

 

 

 

 

10

Stop motor

Press Stop key

Turn OFF the

 

 

 

[FW] terminal

 

 

 

 

11

Run Reverse

Turn ON the [RV]

 

command (optional)

 

terminal

 

 

 

 

12

Stop motor

Turn OFF the

 

 

 

[RV] terminal

 

 

 

 

8