Func.

 

 

Default Value

Set

Name / Description

–FE2 / –FU2 /

Code

Value

 

 

–FR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C091

Debug mode enable

 

00

 

 

• 00 Display

• 01 No display

 

 

 

 

 

 

C101

Up/Down memory mode selection

00

 

 

• 00 Clear last frequency (return to F001)

 

 

 

• 01 Keep last freq. adjusted by UP/DWN

 

 

 

 

 

 

 

C102

Reset mode selection

 

00

 

 

• 00 Cancel trip state at input signal ON

 

 

 

transition, Stops inverter if in Run Mode

 

 

 

• 01 Cancel trip state at signal OFF transi-

 

 

 

tion, Stops inverter if in Run Mode

 

 

 

• 02 Cancel trip state at input signal ON

 

 

 

transition, no effect if in Run Mode

 

 

 

 

 

 

C103

Restart mode after reset

00

 

 

• 00 Restart at 0 Hz

 

 

 

 

• 01 Resume after frequency matching

 

 

 

 

 

 

 

“H” Group: Motor Constants Functions

Func.

 

 

Default Value

Set

Name / Description

–FE2 / –FU2 /

Code

Value

 

 

–FR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H003/

Motor capacity

 

Factory set

 

H203

 

 

 

 

 

 

 

 

 

H004/

Motor poles setting

 

4

 

H204

• 2 poles

• 4 poles

 

 

 

• 6 poles

• 8 poles

 

 

 

 

 

 

H006/

Motor stabilization constant

100.

 

H206

 

 

 

 

 

 

 

 

 

24