Control Circuit Terminals

Terminal

DescriptionRatings and Notes
name

 

 

P24

+24V power for

24VDC supply, 100 mA max.

 

inputs

 

CM1

+24V common

Common for 24V supply, FW,

 

 

TH, inputs 1 to 5, and FM.

 

 

(Note: Do not ground)

PLC

Common for logic

Common for input terminals 1

 

inputs

to 5, jumper to CM1 for sinking,

 

 

jumper to P24 for sourcing

1, 2, 3,

Intelligent

27VDC max. (use P24 or an

4, 5

(programmable)

external supply referenced to

 

discrete logic

terminal CM1), 4,7kȍ input

 

inputs

impedance

FW

Forward/stop

 

 

command

 

11C-11A

Intelligent

Normally open contacts

12C-12A

(programmable)

250VAC / 30VDC, 5A (resistive

 

relay outputs

load) max., 250VAC / 30VDC,

 

 

5A (inductive load) max.

 

 

Minimum load 5VDC, 5mA

TH

Thermistor input

Reference to CM1, min.

 

 

thermistor power 100mW

FM

PWM output

0 to 10VDC, 1.2 mA max.,

 

 

50% duty cycle

2