Error Codes

The L300P series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.

Basic Error Codes

Error

Name

 

Probable Cause(s)

Code

 

 

 

 

 

 

 

 

 

 

 

 

E01

Over current event while at

Inverter output was short-circuited

 

constant speed

• Motor shaft is locked

 

 

• Load is too heavy

E02

Over current event during

• A dual-voltage motor is wired

 

deceleration

incorrectly

 

 

Note: The L300P will over current trip

E03

Over current event during

at nominally 200% of rated current

acceleration

 

 

 

 

 

 

E04

Over current event for other

• DC braking power(A054) set too high

 

conditions

Current transformer / noise error

E05

Overload protection

• Motor overload is detected by the

 

 

electronic thermal function

 

 

 

 

E06

Braking resistor overload

Regenerative braking resistor exceeds

 

 

the usage time or usage ratio

 

 

 

E07

Over voltage

• DC bus voltage exceeds a threshold,

 

protection

due to regenerative energy from motor

 

 

 

E08

EEPROM error

Built-in EEPROM memory experi-

 

 

enced noise, high temperature, etc.

E09

Under-voltage error

• DC bus voltage decreased enough to

 

 

cause a control circuit fault

 

 

 

 

E10

CT error

High electrical noise near inverter

 

(current transformer)

A fault occurred in the built-in CT

 

 

 

E11

CPU error

Built-in CPU had internal error

 

 

 

 

E12

External trip

[EXT] input signal detected

 

 

 

E13

USP (Unattended Start

• When (USP) was enabled, an error

 

Protection)

occurred when power was applied while

 

 

a Run signal was present

 

 

 

E14

Ground fault

• A ground fault was detected between

 

 

the inverter output and the motor. This

 

 

feature protects the inverter, and does

 

 

not protect humans.

 

 

 

 

E15

Input over-voltage

Input voltage was higher than the

 

 

specified value, 60 sec. after powerup

E16

Instantaneous power failure

• Input power removal > 15ms or

 

 

> B002... inverter restarts on Run cmd

 

 

 

 