“P” Group: Expansion Card Functions
Func. |
| Default Value | Set | |
Name / Description | ||||
Code | Value | |||
| ||||
|
|
| ||
|
|
|
| |
|
|
|
| |
P001 | Operation mode on expansion card #1 error | 00 |
| |
| • 00 Trip (stop motor) |
|
| |
| • 01 Continuous operation |
|
| |
|
|
|
| |
P002 | Operation mode on expansion card #2 error | 00 |
| |
| • 00 Trip (stop motor) |
|
| |
| • 01 Continuous operation |
|
| |
|
|
|
| |
P044 | DeviceNet comm watchdog timer | 1.00 |
| |
|
|
|
| |
P045 | Inverter action on DeviceNet comm error | 01 |
| |
| • 00 Trip |
|
| |
| • 01 Decelerate and trip |
|
| |
| • 02 Hold last speed |
|
| |
| • 03 Free run stop |
|
| |
| • 04 Decelerate and stop |
|
| |
|
|
|
| |
P046 | DeviceNet polled I/O: Output instance | 21 |
| |
| number |
|
| |
|
|
|
| |
P047 | DeviceNet polled I/O: Input instance | 71 |
| |
| number |
|
| |
|
|
|
| |
P048 | Inverter action on DeviceNet idle mode | 01 |
| |
| • 00 Trip |
|
| |
| • 01 Decelerate and trip |
|
| |
| • 02 Hold last speed |
|
| |
| • 03 Free run stop |
|
| |
| • 04 Decelerate and stop |
|
| |
|
|
|
| |
P049 | DeviceNet motor poles setting for RPM | 0 |
| |
|
|
|
| |
P050 | • Output frequency on analog reference | 00 / 00 / — |
| |
| signal loss |
|
| |
| • 00 Output freq. forced to 0 Hz; 500ms |
|
| |
| wait to recover |
|
| |
| • 01 Output freq. forced to 0 Hz; no wait to |
|
| |
| recover |
|
| |
| • 02 Output freq. forced to max. freq. A004 |
|
| |
| • 03 Output freq. forced to A020/A220 |
|
| |
|
|
|
|
25