System Programming

System Programming

Programming Interface

System Programming

The system’s Normal programming mode offers several menu options that are accessible from the main menu screen:

Tx Info:

Allows transmitter parameters to be programmed

Groups:

Allows groups of transmitters to be set up

Events:

Allows events and event behavior to be programmed

Acqui:

Allows the datalogging feature to be activated or deactivated

Copy:

Allows data or parameters to be copied from the (controller)

 

configuration to parameters

Config:

Allows system parameters and password to be set

Network: Allows actions on the network to be performed,

 

communication statistics to be consulted, and remote

 

calibrations to be performed

Tests:

Allows each device to be tested sequentially (inputs, outputs,

 

communications, events, etc.) and operation of various

 

parameters to be validated

BACNet:

Allows a device’s BACNet parameters to be set

Wireless: Allows a network of wireless gas detection devices to be configured, monitored, and modified.

Note: Access to the programming functions is password protected. The default password is 2967.

The screen display shown below appears initially. This display can be configured to scroll among the information screens for each device connected to the controller.

If one or more of the connected devices is in an alarm mode, the controller will only scroll between the main information screen and the screens for device(s) in alarm mode. In this case, you must scroll manually to view screens for other devices.

20

96d User Manual

M-511401

 

Honeywell

8/10

Page 23