The first screen presents three options:

System Programming

Tests Menu

The Tests menu provides four main options, divided between two screens. Each of these options offers different capabilities.

The first screen presents three options:

8. Tests Test sequence Start Sim Sequence Maximum load

Test sequence: Enables each output to be activated and validates operation of each controller keypad buttons, display pixels, and various communication protocols.

Start Sim

Sequence: This options starts or stops the Simulation mode, which allows a simulation of a gas concentration over an associated scale range on all transmitters. The simulated gas concentration values are local (on the controller) and do not affect logging functions. (Events will be activated for the simulation but detection devices are not affected.)

Maximum load: Activates all controller components

The second screen option is “Oprt Mode”, which offers three separate operation settings: Normal, Single Tx or Debug.

8. Tests

Manual background Oprt Mode: normal

Normal

Normal controller operation mode

 

Single Tx:

Activates the polling mode on a single transmitter.

Debug:

Activates the service mode to perform a calibration

 

and to test Events without triggering actions.

 

 

 

64

96d User Manual

M-511401

 

Honeywell

8/10

Page 67