Honeywell 96D user manual Specifications

Models: 96D

1 80
Download 80 pages 19.02 Kb
Page 74
Image 74
Specifications

Specifications

Specifications

Power requirements 96D

17-27 Vac, 50/60 Hz, 8.64 VA

 

18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)

Operating temperature range

-20°C to 50°C (-4°F to 122°F)

Operating humidity range

0 to 95% RH (non-condensing)

Operating altitude

Up to 3000 m (9843 ft)

Network capacity

Up to 96 transmitters, 32 per channel

 

Channels 1, 2 = Modbus

 

Channel 3 = Modbus only

Communication

Up to 609m (2,000 ft) per channel

(length of lines)

T-tap maximum = 20m (65 ft) per t-tap,

 

overall total of 40m (130 feet)

User interface

Graphic 122 x 32 dot matrix backlit display

 

User friendly keypad

Visual indicators

Power

Green LED

 

Warn, Alarm, High Alarm Red LED

 

Fault

Amber LED

 

Tx

Amber LED

 

Rx

Green LED

Outputs

4 DPDT relays

Output rating

5A, 30Vdc or 250 Vac (resistive load)

Audible alarm

65dBA at 1 m (3 ft)

Time delays

Programmable Before and After delays

Battery

3 volt lithium battery

Enclosure

Painted aluminum

Dimensions (HxWxD)

9.5” x 14” x 3.5” (24.1 x 35.6 x 8.9 cm)

Certifications

ANSI/UL 61010-1

 

CAN/CSA C22.2 No. 61010-1

 

ETL 116662

 

 

 

M-511401

96d User Manual

71

8/10

Honeywell

 

Page 74
Image 74
Honeywell 96D user manual Specifications