Detection Menu

System Programming

Tx Info Menu

Detection Menu

The detection menu (available only for devices with addresses between 1 and 96) displays the detection range (scale: 0-100.0) and the unit of measurement (unit: %) for the selected component. If a transmitter uses the Modbus protocol, the detection parameters are automatically defined during network configuration and are not editable. Vulbus protocols must be manually defined by the programmer.

The detection scale is between 0 and the maximum value (0.00) and the unit of measurement is either ppm or percent (% for oxygen and % LEL for combustibles).

The detection menu is not available for the VA301R or VA301AP.

1. Tx Info

001

-Detection-

scale: 0-0.00

unit: %

Programming or modifying the scale range or unit:

Use the arrows to move the cursor to the scale or unit option

Press Enter and use the arrow to increase or decrease the value

Press Enter when the desired value is obtained