Front view shown

You must make the connections between the facility and the HP POD 240e NA. For configuration and installation instructions, consult with HP.

Access control

The HP POD 240e NA is equipped with standard key lock hardware for each personnel entry door and external electrical cabinet. Each personnel entry door includes a door access contact that can be connected to your facility access control system.

Additional options for controlled access include the following:

Electronic card reader

12-digit access control code keypad

Magnetic lock on each personnel access door and dynamic hot aisle door

Fire, safety, and access notifications

Dry contacts are provided to allow the connection between the HP POD 240e NA and your facility. If the HP POD 240e NA is connected to your facility systems, then the alarm conditions of the HP POD 240e NA can be detected by the facility systems.

It is your responsibility to facilitate these connections. HP can make these connections when specifically contracted to deliver these services and a SOW has been drafted, reviewed, and signed for delivery services.

You must provide an independent connection for each system listed in the following table.

Alarm

Description

 

 

Fire prevention alarm

Smoke is detected in the HP POD 240e NA.

Access control

A door of the POD has been opened.

EPO

The EPO system is activated by manually pressing the

 

EPO button or by a thermal event, and the HP POD

 

240e NA is shut down.

 

 

Supported facility connections 19

Page 19
Image 19