Overview

About this document

This document outlines the site preparation requirements for an HP Performance Optimized Datacenter 240e NA. You must provide a qualified architectural or consulting engineering team to generate site-specific documents for each HP POD 240e NA installation, including final site drawings. Your site installation design must comply with all local and national regulations, ordinances, codes, and the specifications listed in this document.

Safety and NEC compliance

The HP POD 240e NA is Listed to UL 69050 Part 1 and Part 22 as an Information Technology Product and Classified in accordance with the National Electric Code NFPA 70.

The HP POD 240e NA is not habitable or suitable for human occupancy. The HP POD 240e NA is Listed as a Product that provides Service Access Areas for periodic maintenance and service. Access to these areas must be controlled and available for use only by owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD 240e NA components. For more information, see "HP POD 240e NA regulatory compliance (on page 32)."

IMPORTANT: Before installing the HP POD 240e NA, consult your local AHJ for applicable regulations and to review site-specific location guidelines. If needed, obtain any necessary permits.

Additional considerations for safety and NEC compliance are as follows:

The HP POD 240e NA is Listed as an Information Technology Equipment Product to UL 60950.

The HP POD 240e NA is evaluated as a "non-inhabitable product" that provides "service access" areas for customer-authorized, qualified, and trained service personnel.

The electrical connections of the HP POD 240e NA are evaluated as feeder connections for connection to an existing facility. The electrical connections are not suitable as "service entrance" for connection to the utility.

The HP POD 240e NA is designed for stationary installation outdoors in a Pollution Degree 3 environment, in restricted access locations, and with field wiring terminals provided for permanent supply connections.

The HP POD 240e NA meets the ratings in the following table.

Feature

Specification

 

 

Category

Rated Overvoltage Category III

Protection

Surge protection device

Class

Class1

Ambient temperature

2°C to 54°C (35.6°F to 129.2°F)

Relative humidity

0% to 100% humidity

Enclosure

NEMA 3R

Overview 5

Page 5
Image 5
HP Performance Optimized Data Center (POD) 240a manual Overview, About this document, Safety and NEC compliance